background image

18

Publication CC-QS015A-EN-P - November 2009

Chapter 1

       Product Integration

Time settings are intended to help make sure that only valid objects of the right size, moving 
at the right speed, can initiate and maintain a muting sequence. 

You may want to add a few seconds to some of your calculations to allow for variations.

Notice that the Connecting diagram shows a lamp, as well as muting sensors connected to 
GPIO1 and GPIO2, and that IN1 is labeled Start/Mute override. In this application a Muting 
Lamp is required for safety purposes to warn personnel in the area when the light curtain is 
muted.

13.

Review the Additional Settings.

a. Make sure that the Muting Lamp monitored box is checked.

Muting lamp monitoring means that should the muting lamp fail, short, or open, the 
MSR42 controller will sense it and not initiate or maintain muting. In applications where a 
muting lamp is required, generally the muting lamp is required to be monitored.

b. Because you entered a t(mdo) time earlier, leave the Mute dependent override box 

checked.

c. In the Muted light curtain section, note that GuardShield Micro 400 is selected and 

disabled and make sure that the Light curtain interruption monitored box is checked.

Time Setting

Description

t(sens)

Since both S1 and S2 or both S3 and S4 sensors must be broken simultaneously to initiate a muting sequence, 
these sensors should be spaced no further apart than the length of the smallest typical load. Calculate how 
long a load takes from the time it first reaches S1 until it reaches S2 (or S3 until it reaches S4), based on the 
speed of the conveyor. This is the t(sens) time for your system.

t(espe)

The t(espe) field is disabled until you check the Light curtain interruption monitored checkbox under Additional 
Settings. The t(espe) of your system is the time from the moment a load reaches the second sensor (S2 from 
the right or S3 from the left) until it enters the light curtain sensing field. Once the light curtain is muted, the 
load must interrupt the light curtain within 3 seconds. Therefore, the second sensor must be placed within 3 
seconds travel time from the light curtain. t(espe) should be no longer than 3 seconds except in extraordinary 
circumstances supported by the risk assessment.

t(mute)

This setting establishes the maximum length of time the light curtain remains muted. Calculate the length of 
time it takes the load to travel from the point where it first reaches the second sensor until the trailing edge of 
the load leaves the light curtain based on the speed of the conveyor. This is the minimum t(mute) for your 
system, which is entered in minutes.

t(mdo)

This setting establishes the maximum length of a Mute Dependent Override. Occasionally, a load may stop 
within the light curtain sensing field. It may be difficult to move the load past the light curtain sensing field 
with a safe stop in effect. Mute Dependent Override is a function that lets a safety stop be paused and muting 
to be re-initiated for the duration of the t(mdo) setting, which lets the load move beyond the light curtain 
sensing field. As soon as the load moves past the light curtain sensing field, muting ceases. If the hazardous 
area is in clear view of the operator and no personnel or objects are in the hazard area, Mute Dependent 
Override can be initiated, in this case, by pressing and releasing the Start/Reset button. Calculate the time it 
takes the load to travel from the point where it first reaches the second sensor (S2 from the right, or S3 from 
the left) until the trailing edge of the load leaves the light curtain sensing field, based on the speed of the 
conveyor.

t(msdel)

In some instances, loads may have gaps that the first two sensors might sense through as the load passes. 
This could lead to a muting error. One method to avoid such errors is to delay the sensors’ response to allow 
for seeing through gaps. The t(msdel) configures that delay time. Unless the gap is very long or the load is 
moving very slowly, the gap is present for only a short time. In most instances, the default 0.050 is suitable. 
Leave this value set at 0.050.

Summary of Contents for Allen-Bradley GuardShield Micro 400

Page 1: ...Bidirectional 4 sensor T type Muting With MSR42 Relay Connected Components Building Block Catalog Numbers MSR42 MicroLogix 1100 GuardShield Micro 400 Light Curtains Quick Start...

Page 2: ...by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written pe...

Page 3: ...nnected Components Building Block Outline Follow the path below to complete your connected components building block ESC OK Chapter 1 Product Integration Chapter 2 System Validation and Application Ti...

Page 4: ...4 Publication CC QS015A EN P November 2009 Where to Start...

Page 5: ...hese Steps 10 Understand the Safety Function 10 Set Up the Configuration and Diagnostic Software 12 Configure the MSR42 Safety Relay 13 Download the Configuration 19 Confirm the Configuration 22 Chapt...

Page 6: ...6 Publication CC QS015A EN P November 2009 Table of Contents...

Page 7: ...Connected Components Building Blocks Overview CD publication CC QR001 The CD provides bills of materials BOM CAD drawings for panel layout and wiring control programs Human Machine Interface HMI scre...

Page 8: ...ding Blocks Overview CD publication CC QR001 Provides files for the Connected Components Building Blocks Position Control Connected Components Building Block Quick Start publication CC QS003 Provides...

Page 9: ...ublication CC QS001 verifying that you have completed the hardware design and installation as well as software installation What You Need Personal computer Connected Components Building Blocks Overvie...

Page 10: ...nd the Safety Function Two separate safety functions are provided 1 The GuardShield Micro 400 light curtains and MSR42 safety relay provide a bidirectional four sensor T type muting function 2 The E s...

Page 11: ...anelView START RESET button may be used to start or reset the safety systems just like the Start Reset push button Safety Systems Diagram IMPORTANT If the operator stationed at the PanelView terminal...

Page 12: ...Curtains a Go to Related Links on the right side of the page and choose Safety Software ZIP b Save the zip file to your personal computer c Unzip the file d Run the SetupDiagnosticAndConfiguration_Vx...

Page 13: ...ct Micro 400 Light Curtain from the Micro 400 Inputs pull down menu 2 Edit the settings as shown a Choose Manual b Leave Stop Delay set to No c Choose Resolution 30 mm d From the Protective height pul...

Page 14: ...s have been added to the Design Output diagram 4 On the Configuration dialog box select Start from the IN1 Inputs pull down menu In addition to the Micro 400 Light Curtains a NO momentary push button...

Page 15: ...lication the Start Release circuit goes from 24V through one auxiliary normally closed NC contact of each 100S contactor to the MSR42 relay Similar to EDM if either or both of these NC contacts are op...

Page 16: ...d passes in sequence the last two sensors An object passing the sensors in the proper sequence and within the configured time constraints is permitted to pass though the light curtains without trigger...

Page 17: ...oad into consideration when mounting the sensors The minimum load must be long enough to be in front of both S1 and S2 or S3 and S4 sensors simultaneously The Muting Help dialog box also provides defi...

Page 18: ...the light curtain is muted the load must interrupt the light curtain within 3 seconds Therefore the second sensor must be placed within 3 seconds travel time from the light curtain t espe should be no...

Page 19: ...save the configuration as 4sensor T type muting 16 Do not exit the MSR42 configuration and diagnostic software Download the Configuration 1 Write down the device number from the label on the side of...

Page 20: ...face into an available USB port on your personal computer 10 Note the new COM port that appears in the list This is the port assigned to the Optical Interface which you will need to select in the Conf...

Page 21: ...gned by Windows Device Manager 15 Click OK 16 From the File menu choose PC MSR42 Download 17 When prompted type the password ABGM 18 On the Controller Description dialog box type the six digit Device...

Page 22: ...og box review the configuration and check the confirmation box 2 Click Continue 3 When prompted to print the document click No The software saves a copy that can be printed later from the File menu 4...

Page 23: ...elpful diagnostic features that are described in the MSR42 Safety Base Module Operation Manual publication 440R IN017 and the Configuration Tool for MSR42 GS Micro 400 and Safe 2 4 Light Curtains Soft...

Page 24: ...24 Publication CC QS015A EN P November 2009 Chapter 1 Product Integration Notes...

Page 25: ...nt Verify that all components of the system are assembled and wired per the Bill of Materials Assembly Diagrams and Wiring Diagrams provided for this Connected Components Building Block and as require...

Page 26: ...ng The 100S contactors do not energize Guarded motion does not start The red stacklight is on 3 Press and release the Start Reset button 4 Check the following The 100S contactors energize Guarded moti...

Page 27: ...he green stacklight is on Light Curtain Function 1 Break the light curtain beam and keep it broken taking care not to block any sensors 2 Check the following The two 100S contactors de energize Guarde...

Page 28: ...heck the following S4 switches as the load passes S3 switches as the load passes The muting lamp turns on The load passes through the light curtain without the system shutting off The muting lamp turn...

Page 29: ...break the light curtain beam taking care not to block any sensors 4 Check the following The safety output turns off The two 100S contactors de energize Guarded motion stops The red stacklight turns o...

Page 30: ...not blinking The green stacklight turns on 3 As soon as the load clears the light curtain break the light curtain beam taking care not to block any sensors 4 Check the following The safety output turn...

Page 31: ...as the signals driving them change The following pages illustrate a typical sequence of PanelView screens Confirm that the system and PanelView screens operate as expected by following this sequence...

Page 32: ...ss START RESET for three seconds and release The system should start running Note that the START RESET button is green only when the system is ready for a Start Reset It is no longer green once the sy...

Page 33: ...cation Tips Chapter 2 As the load leaves S2 muting ends 4 Press the E stop The screen updates in response 5 Press MORE INFO 6 Press RETURN 7 Twist and release the E stop 8 Press START RESET for three...

Page 34: ...interrupted 10 Press MORE INFO 11 Press RETURN 12 Remove the object interrupting the light curtain Once the light curtain is no longer interrupted the display returns to the Ready for START RESET scr...

Page 35: ...configured t espe the time it should take a load to travel between S2 and the light curtain the muting lamp begins to blink The screen reflects the muting error 16 Press MORE INFO 17 Press RETURN 18 M...

Page 36: ...red t mdo expires 23 Carefully disconnect then reconnect one of the light curtain cables from the MSR42 relay at its RJ45 socket TIP When the START RESET button is green it may be used in place of the...

Page 37: ...Publication CC QS015A EN P November 2009 37 System Validation and Application Tips Chapter 2 24 Press MORE INFO 25 Press RETURN 26 Press and hold START RESET for 10 seconds...

Page 38: ...38 Publication CC QS015A EN P November 2009 Chapter 2 System Validation and Application Tips Notes...

Page 39: ......

Page 40: ...l You can contact Customer Support for initial help in getting your product up and running New Product Satisfaction Return RockwellAutomationtestsallofitsproductstoensurethattheyarefullyoperationalwhe...

Reviews: