Maintenance
Repair
102
MagneMotion
Rockwell Automation Publication MMI-UM037A-EN-P - April 2020
AC Fuse
1.
Turn off power to the MM LITE Power Supply and unplug the power cable.
NOTE:
When unplugging the cable from the power supply, the lock on the connector
must be released before disconnecting the cable.
2.
Open the Power Entry Module (PEM), shown in
, by inserting a small
flat-blade screwdriver into the slot at the top and pressing outward as shown in
Figure 35: Open the Power Entry Module
3.
Remove the fuse module from the PEM by inserting a small flat-blade screwdriver
into the slot at the top and pressing outward as shown.
Figure 36: Remove the PEM Fuse Module
4.
Remove the old fuse.
5.
Install a new fuse.
Fuse Type
Fuse Location
250V, 10 A time-lag fuses
Single fuse on the right-hand side.
Single fuse on the left-hand side.