EM-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
58 of 71
ser
v
ice or maintenance. Allo
w
heater to cool before
ser
v
icing.
Before e
v
ery heating season, a contractor q
u
alified in
the installation and ser
v
ice of gas-fired heating
eq
u
ipment m
u
st perform a thoro
u
gh safety
inspection of the heater.
For best performance, the gas, electrical, thermostat
connections, t
u
bing,
v
enting, s
u
spensions and
o
v
erall heater condition sho
u
ld be thoro
u
ghly
inspected.
NOTE:
Gas flo
w
and b
u
rner ignition are among the
first things that sho
u
ld be inspected.
Please
See Page 58
for s
u
ggested items to inspect.
Installation Code and Annual Inspections:
All installation and ser
v
ice of ROBERTS GORDON
®
eq
u
ipment m
u
st be performed by a contractor
q
u
alified in the installation and ser
v
ice of eq
u
ipment
sold and s
u
pplied by Roberts-Gordon LLC and
conform to all req
u
irements set forth in the
ROBERTS GORDON
®
man
u
als and all applicable
go
v
ernmental a
u
thorities pertaining to the
installation, ser
v
ice and operation of the eq
u
ipment.
To help facilitate optim
u
m performance and safety,
Roberts-Gordon LLC recommends that a q
u
alified
contractor cond
u
ct, at a minim
u
m, ann
u
al
inspections of yo
u
r ROBERTS GORDON
®
eq
u
ipment
and perform ser
v
ice
w
here necessary,
u
sing only
replacement parts sold and s
u
pplied by Roberts-
Gordon LLC.
The Vicinity of the Heater
Do not store or
u
se flammable objects, liq
u
ids or
v
apors near the heater.
Immediately remo
v
e these items if they are present.
See Page 6, Section 3
.
Vehicles and Other
Objects
Maintain the clearances to comb
u
stibles.
Do not hang anything from, or place anything on, the heater.
Make s
u
re nothing is lodged
u
nderneath the reflector, in bet
w
een the t
u
bes or
in the decorati
v
e or protecti
v
e grilles (incl
u
ded
w
ith select models).
Immediately remo
v
e objects in
v
iolation of the clearances to comb
u
stibles.
See Page 6, Section 3
.
Reflector
S
u
pport reflector
w
ith reflector hanger and s
u
pport strap.
Reflector m
u
st not to
u
ch t
u
be.
Make s
u
re there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make s
u
re reflectors are correctly o
v
erlapped.
See Page 20, Section 6.5.1
.
Clean o
u
tside s
u
rface
w
ith a damp cloth.
Vent Pipe
Venting m
u
st be intact. Using a flashlight, look for obstr
u
ctions, cracks on the
pipe, gaps in the sealed areas or corrosion.
The area m
u
st be free of dirt and d
u
st. Clean as req
u
ired.
Remo
v
e any carbon deposits or scale
u
sing a
w
ire br
u
sh.
See Page 31, Section 8
.
Outside Air Inlet
Inlet m
u
st be intact. Look for obstr
u
ctions, cracks on the pipe, gaps in the
sealed areas or corrosion.
The area m
u
st be free of dirt and d
u
st. Clean and reinstall as req
u
ired.
Tubes
Make s
u
re there are no cracks.
Make s
u
re t
u
bes are connected and s
u
spended sec
u
rely.
See Page 12, Section 6
.
Make s
u
re there is no sagging, bending or distortion.
Clean or replace as req
u
ired.
Gas Line
Check for gas leaks.
See Page 37, Section 9
.
Summary of Contents for Energytube EM-115
Page 2: ......
Page 4: ......
Page 6: ......
Page 69: ...SECTION12 TROUBLESHOOTING 63 of 71 12 3 Troubleshooting Flow Chart ...
Page 70: ...EM SERIES INSTALLATION OPERATION AND SERVICE MANUAL 64 of 71 ...
Page 72: ...EM SERIES INSTALLATION OPERATION AND SERVICE MANUAL 66 of 71 12 5 Pneumatic Connections ...
Page 74: ...EM SERIES INSTALLATION OPERATION AND SERVICE MANUAL 68 of 71 ...
Page 78: ......
Page 80: ......
Page 81: ......