Operations 7
48
Switched Power Distribution Unit
EN
Enabling/disabling UPS voltage polling:
With a UPS record configured, the PDU by default
enables voltage polling of the UPS. This feature
may be enabled or disabled using the Set UPS
VPoll command.
To enable/ disable UPS voltage polling:
At the Switched PDU: prompt, type set ups vpoll
and press Enter.
At the prompt, enter the index number for the
UPS record to be changed and press Enter.
At the prompt, type on or off, and press Enter.
Example
The following command disables voltage polling
for the record at index number 2:
Switched PDU: set ups vpoll<Enter>
UPS UPS Voltage
Index Type Polling
1 Liebert On
2 MGE On
Select UPS(1-8): 2<Enter>
Voltage Polling: Off<Enter>
Adding an infeed to a UPS:
The Set UPS AddInfeed command adds a logical
association of an infeed to a UPS.
To add an infeed to a UPS:
At the Switched PDU: prompt, type set ups
addinfeed and press Enter.
At the prompt, enter the index number for the
UPS record to be changed and press Enter.
At the prompt, type the absolute infeed ID of the
desired infeed, and press Enter.
Example
The following command associates infeed .aa to
UPS record at index number 1:
Switched PDU: set ups addinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert
2 MGE .AA
Select UPS(1-8): 1<Enter>
Infeed ID: .aa<Enter>
Removing an infeed from a UPS:
The Set UPS DelInfeed command removes a
logical association of an infeed from a UPS.
To remove an infeed from a UPS:
At the Switched PDU: prompt, type set ups delin-
feed and press Enter.
At the prompt, enter the index number for the
UPS record to be changed and press Enter.
At the prompt, type the absolute infeed ID of the
desired infeed, and press Enter.
Example
The following command removes the association
of infeed .aa from UPS record at index number 2:
Switched PDU: set ups delinfeed<Enter>
UPS UPS Infeed
Index Type IDs
1 Liebert .AA
2 MGE .AA
Select UPS(1-8): 2<Enter>
Infeed ID: .aa<Enter>
Displaying UPS configuration:
The Show UPS command displays information
about all UPS devices.
•
UPS Type and Host/IP address
•
UPS SNMP port and community string
•
SNMP Objects OID values and expected return
values
To display UPS configuration information:
At the Switched PDU: prompt, type show ups
and press Enter.
Example
The following command displays UPS configura-
tion information:
Switched PDU: show ups<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
Voltage Polling: ON
SNMP Configuration
Community String: public
SNMP Port: 162
SNMP Objects/Expected
Values
Voltage:
.1.3.6.1.2.1.33.1.4.4.1.2.1
Utility Status:
.1.3.6.1.2.1.33.1.4.1.0
On Battery: 0x5
On Utility: 0x3
More (Y/es N/o):