Operations 7
Switched Power Distribution Unit
35
EN
Example
The following command displays all outlet infor-
mation:
Switched PDU: show outlets<Enter>
Outlet Outlet Wakeup Post-On
ID Name State Delay(sec)
.A1 DataServer_1 On 0
.A2 WebServer_1 On 0
.A3 FileServer_1 On 0
.A4 TowerA_Outlet4 On 0
.A5 TowerA_Outlet5 On 90
.A6 TowerA_Outlet6 On 0
.A7 TowerA_Outlet7 On 0
.A8 TowerA_Outlet8 On 0
.A9 TowerA_Outlet9 On 0
.A10 TowerA_Outlet10 On 0
.A11 TowerA_Outlet11 On 0
.A12 TowerA_Outlet12 On 0
.A13 TowerA_Outlet13 On 0
.A14 TowerA_Outlet14 On 0
.A15 TowerA_Outlet15 On 0
.A16 TowerA_Outlet16 On 0
More (Y/es N/o):
Outlet Options:
Sequence Interval: 2 seconds
Reboot Delay: 15 seconds
Input Feed Administration
Creating a descriptive infeed name:
The Set Infeed Name command assigns a de-
scriptive name to an infeed. This descriptive
name is displayed when the Show Traps com-
mand is issued.
To create a infeed name:
At the Switched PDU: prompt, type set infeed
name followed by the absolute infeed name, then
a descriptive name of up to 24 alphanumeric and
other typeable characters - (ASCII 33 to 126
decimal) are allowed; spaces are not allowed.
Press Enter.
Example
The following command adds the descriptive
name HQ_1_Infeed_A to the infeed on the
Switched PDU:
Switched PDU: set infeed name .aa
HQ_1_Infeed_A<Enter>
Setting the infeed operational voltage
The Set Infeed Voltage command is use to edit
the input operational voltage.
To set the infeed operational voltage:
At the Switched PDU: prompt, type set infeed
voltage, followed by the absolute infeed name,
and a value from 0 to 480. Press Enter.
Example
The following commands sets the operational
voltage for input .AA to 100V:
Switched PDU: set infeed voltage .aa
100<Enter>
Setting the infeed maximum load capacity
The Set Infeed LoadMax command is use to edit
the input maximum load capacity.
To set the infeed maximum load capacity:
At the Switched PDU: prompt, type set infeed
loadmax, followed by the absolute infeed name,
and a value from 1 to 255 (in amperes). Press
Enter.
Example
The following commands sets the maximum load
capacity for input .AA to 15 amperes:
Switched PDU: set infeed loadmax .aa 15<Enter>
Displaying infeed information:
The Show Infeeds command displays information
about all infeeds. This information includes the
absolute and descriptive infeed names, opera-
tional voltages and maximum load capacities.
To display tower information:
At the Switched PDU: prompt, type show infeeds
and press Enter.
Example
Switched PDU: show infeeds<Enter>
Input Input Input Input
Feed ID Feed Name Feed Voltage Feed Capac
.AA HQ_1_Infeed_A 100 15
.AB HQ_1_Infeed_B 120 20
.BA HQ_2_Infeed_A 120 30
.BB HQ_2_Infeed_B 120 30