Operations 7
38
Switched Power Distribution Unit
EN
To create an Environmental Monitor name:
At the Switched PDU: prompt, type set envmon
name followed by the absolute environmental
monitor name, then the descriptive name of up to
24 alphanumeric and other typeable characters -
(ASCII 33 to 126 decimal) are allowed; spaces
are not allowed. Press Enter.
Example
The following command adds the descriptive
name Florida_HQ_1to the Environmental Monitor:
Switched PDU: set envmon name .a Flor-
ida_HQ_1<Enter>
Creating a descriptive temperature/humidity
sensor name:
The Set Envmon THS Name command assigns a
descriptive name to a temperature/humidity sen-
sor. This descriptive name is displayed when the
Evnmon command is issued.
To create an temperature/humidity sensor name:
At the Switched PDU: prompt, type set envmon
ths name followed by the absolute name of the
temperature/humidity sensor, then the descriptive
name of up to 24 alphanumeric and other type-
able characters - (ASCII 33 to 126 decimal) are
allowed; spaces are not allowed. Press Enter.
Example
The following command adds the descriptive
name T/H2_Florida_HQ_1 to the second tem-
perature/humidity sensor:
Switched PDU: set envmon ths name .a2
T/H2_Florida_HQ_1<Enter>
Serial Port Administration
Creating a descriptive serial port name:
The Set Port Name command assigns a descrip-
tive name to a serial port. You may use this
name in commands that require a port name as
an alternative to using the port’s absolute name.
To create an port name:
At the Switched PDU: prompt, type set port
name followed by the absolute outlet name, then
a descriptive name of up to 24 alphanumeric and
other typeable characters - (ASCII 33 to 126
decimal) are allowed; spaces are not allowed;
port names are not case sensitive. Press Enter.
Example
The following command adds the descriptive
name Rack1 to Console port:
Switched PDU: set port name console
Rack1<Enter>
Setting the serial ports data-rate:
The Set Port Speed command sets the default
data-rate for the serial port.
Valid data-rates are 1200, 2400, 4800, 9600,
19200, 38400, 57600 and 115200.
To set the serial port data-rate:
At the Switched PDU: prompt, type set port
speed, follow by the data-rate and press Enter.
Example
The following command sets the serial ports data-
rate to 38400 BPS:
Switched PDU: set port speed 38400<Enter>
Enabling or disabling active signal checking
for serial connections:
The Set Port Dsrchk command enables or dis-
ables active signal checking for serial connections
to devices attached to any of the available serial
ports.
To enable or disable active signal checking for serial
connections:
At the Switched PDU: prompt, type set port
dsrchk console, on or off, and press Enter.
Setting the serial port timeout value:
The Set Port Timeout command is used to set the
serial port inactivity timeout period. The timeout
period defines the maximum period of inactivity
before automatically closing the Pass-Thru ses-
sion. The valid range for the period parameter is
0 to 5 (in minutes). The default period is 5.
Note!
Setting the timeout to ‘0’ disables the
timer.