20081825
58
GB
Start-up, calibration and operation of the burner
6.16
Ignition failure
If the burner does not switch on, there is a lockout within 3s of the
electrical supply reaching the fuel valve.
It may be that the fuel does not arrive at the combustion head
within the safety time of 3s.
In this case increase fuel ignition flow rate.
6.17
Burner flame goes out during operation
If the flame accidentally goes out while running, the burner goes
into lockout within 1 second.
6.18
Stopping of the burner
The burner can be stopped by:
intervening on the disconnecting switch of the electrical sup-
ply line, located on the boiler panel;
removing the transparent protection 30) Fig. 5 on page 15,
after unscrewing the relative screw.
There are now two possibilities:
–
using the operator panel according to the manual lockout pro-
cedure on page 42;
–
using the ON-OFF switch of Fig. 34 on page 36.
6.19
Final checks
With the burner running
With the burner off
At the next start-up
Tab. U
6.20
Fan motor and pump motor lockout
If the motor does not start, it could be because of a thermal relay
intervention due to its incorrect calibration or problems with the
motor or the main power supply, to release press the button of the
thermal relay, see “Calibration of the thermal relay” on page 23.
WARNING
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row.
If the burner locks out for a third time, contact the
customer service.
DANGER
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
WARNING
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
Open the thermostat/pressure switch TL
Open the thermostat/pressure switch TS
the burner must stop
Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
Turn the air pressure switch knob to the maximum end of
scale position
the burner must stop in lockout
Obscure the flame sensor
the burner must stop in lockout due to flame loss
Switch off the voltage
Disconnect the minimum gas pressure switch connector
see “Minimum gas pressure switch” on page 41
Switch off the voltage
Disconnect the maximum oil pressure switch connector
the burner does not start and stops in phase 12, the display
shows: “OFF S”.
Switch off the voltage
Disconnect the minimum oil pressure switch connector
see “Minimum oil pressure switch” on page 41
Switch off the voltage
Disconnect the maximum gas pressure switch connector
the burner does not start and stops in phase 12, the display
shows: “OFF S”.
Obscure the flame sensor
the burner must stop in lockout due to ignition failure
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......