Start-up, calibration and operation of the burner
NOTE:
If an error occurs during the backup process, the display
screen shows a negative value.
Refer to diagnostic code 137 to determine the cause of the
error (see section “List of parameters” on page 52).
6.14.2 Restore
To perform the restore procedure, proceed as follows:
access the Parameters Level referring to “Access procedure
with password” on page 44.
The display screen displays the parameters group
400
.
With the key
“-”
:
Select the parameters group
000
:
The
000
parameter blinks, confirm using the
“i/reset”
key:
The display screen shows parameter
050
blinking:
Confirm with the key
“i/reset”
:
The parameter
bAC_UP
appears on the display screen:
With the key
“+”
select the
rEStorE
parameter
Confirm with the key
“i/reset”
:
The display shows the following value.
Use the button
“+”
:
The value will be set to
1
. Value 1 is flashing:
confirm with the button
“i/reset”
to activate the
restore
process.
WARNING
It is advisable to perform a backup every time
that a parameter is changed, after checking
that the modification carried out is correct.
WARNING
Use this procedure when replacing equipment
with a parts code. In this way it is possible to have
the default parameters already memorised or
those memorised during the start-up.
This procedure cannot be carried out on
equipment coming from other burners.
D9023
P
V
%
s
min
h
D12140
h min s
%
P
/reset
D
1
2141
h min s
%
P
/reset
D12142
h min s
%
P
V
D12146
h min s
%
P
V
/reset
D12143
h min s
%
P
V
D121
44
h min s
P
V
/reset
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......