Faults - Possible causes - Solutions
22
OFF S
#
Safety circuit/Burner flange
0
Safety circuit open /Burner flange open
1
Safety circuit open /Burner flange open - Alarm lockout at
start
3
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
5
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
17
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
19
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
21
Safety circuit open /Burner flange open, extraneous light -
Alarm lockout at start
23
Safety circuit open /Burner flange open, extraneous light,
air pressure, fuel pressure - Alarm lockout at start
65
Safety circuit /Burner flange open, POC - Alarm lockout at
start
67
Safety circuit open /Burner flange open, extraneous light,
POC - Alarm lockout at start
69
Safety circuit open /Burner flange open, air pressure, POC
- Alarm lockout at start
71
Safety circuit open /Burner flange open, extraneous light,
air pressure, POC - Alarm lockout at start
81
Safety circuit open /Burner flange open, fuel pressure,
POC - Alarm lockout at start
83
Safety circuit open /Burner flange open, extraneous light,
air pressure, POC - Alarm lockout at start
85
Safety circuit open /Burner flange, air pressure, fuel
pressure, POC - Alarm lockout at start
87
Safety circuit open /Burner flange, extraneous light, air
pressure, fuel pressure, POC - Alarm lockout at start
50 ÷ 58
#
Internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
60
0
Internal error: no valid load checking device
Carry out a reset; if the error arises repeatedly, replace the
control box
65 ÷ 67
#
Internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
70
#
Fuel/air checking error: Calculation position in
modulation
23
Invalid load
No valid load
26
Curve points not defined
Adjust the curve points of all the actuators
71
#
Special position not defined
0
Standby position
Set the standby position of all the servomotors used
1
Pre-purging position
Set the pre-purging position of all the servomotors used
2
Post-purging position
Set the post-purging position of all the servomotors used
3
Ignition position
Set the ignition position of all the servomotors used
72
#
Fuel/air internal checking error
Carry out a reset; if the error arises repeatedly, replace the
control box
73
#
Fuel/air internal checking error: multistep calculation
position
23
Position calculation, invalid stage load
No valid load
26
Position calculation, stage curve points not defined
Adjust the curve points of all the servomotors
Error
code
Diagnostic code
Meaning of the LMV 26... system
Recommended measures
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......