Start-up, calibration and operation of the burner
145
Peripheral address for Modbus
Set values:
1 ... 247
1
-
Modification
1
247
1
1
Service Mode
146
Baud Rate for Modbus
Set values:
0 = 9600
1 = 19200
1
-
Modification
0
1
1
1
Service Mode
147
Parity for Modbus
0 = none
1 = odd
2 = even
1
-
Modification
0
2
1
0
Service Mode
148
Selection of the burner operation during the interrup-
tion of the switch-over with the system of remote man-
agement.
Set values:
With
modulating operation
the settings of the values
are the following:
0...19.9 = burner switched off
20...100 = 20...100% modulation field of the burner.
With
stage operation
:
0 = burner off P1, P2, P3
No setting = no function in the event of communication
interruption
1
%
Modification /
zero setting
0%
100%
0.1%
Not defined
Service Mode
161
Total number of errors
1
-
Reading only
0
65535
1
0
Info mode
162
Hours of operation (that can be reset)
1
h
Reset
0 h
999999h
1 h
0h
Info mode
163
Total hours of power supply to control box
1
h
Reading only
0h
999999h
1h
0h
Info mode
164
Total number of start-ups (that can be reset)
1
-
Reset
0
999999
1
0
Info mode
166
Total number of start-ups
1
-
Reading only
0
999999
1
0
Info mode
167
Volumetric delivery of fuel in the selected unit of meas-
urement (that can be reset)
1
m
3
, l,
ft
3
, gal
Reset
0
99999999
1
0
Info mode
200
BURNER CHECKS (fuel 0)
201
Burner operation mode (fuel supply line, modulating/
stage, servomotors, etc.)
-- = not defined (eliminate curves)
1 = Gmod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2 stage
6 = Lo 3 stage
7 = Gmod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod only gas actuator
20 = Gp1 mod only gas actuator
21 = Gp2 mod only gas actuator
22 = Lo mod only oil actuator
1
-
Modify/set to
zero
1
22
1
Not defined
Service Mode
208
Stopping of the program
0 = deactivated
1 = pre-purging (Ph24)
2 = Ignition (Ph36)
3 = Interval 1 (Ph44)
4 = Interval 2 (Ph52)
1
-
Modification
0
4
1
0
Service Mode
210
Alarm as the pre-purging phase begins;
0 = Deactivated;
1 = Activated
1
-
Modification
0
1
1
0
Service Mode
211
Uphill train fan motor
1
s
Modification
2s
60s
0.2s
2s
Service Mode
212
Maximum time to reach low flame
1
s
Modification
0.2s
10 min
0.2s
45s
Service Mode
Parameter
No. of
elements
Unit of
measure-
ment
Modifica-
tion
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
Description
Min.
Max.
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......