Maintenance
7.2.4
Measuring the flame signal
The burner is fitted with a sensor to check that a flame is present.
The minimum current for control box operation is 70 µA. The op-
erator Panel displays “30%” (see “List of parameters” on
page 52, parameter 954).
The burner provides a much higher current, so controls are not
normally required.
If, however, you want to measure the current of the flame sensor,
follow the instructions as described in “Maintenance programme”
on page 59.