Faults - Possible causes - Solutions
If faults arise in ignition or operations, the burner performs a
“safety stop”, which is signalled by the red burner lockout LED.
The display of the operator panel visualises alternately the lock-
out code and the relative diagnostic.
To restore start-up conditions, refer to the “Reset procedure” on
page 43.
When the burner starts up again, the red LED goes out.
8.1
List of error codes
8
Faults - Possible causes - Solutions
WARNING
In the event the burner stops, in order to prevent
any damage to the installation, do not unblock the
burner more than twice in a row.
If the burner locks out for a third time, contact the
customer service.
DANGER
In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
Error
code
Diagnostic code
Meaning of the LMV 26... system
Recommended measures
No Comm
No communication between LMV 26... and RDI21…
Check the wiring between the control box REC 27.100A2 and
display RDI21…
2
#
No flame at the end of TSA1
1
No flame at the end of safety time 1 (TSA1)
2
No flame at the end of safety time 2 (TSA2)
4
No flame at the end of safety time 1 (TSA1)
(software version
V02.00)
3
#
Air pressure error
0
Air pressure switch off
1
Air pressure switch on
4
Air pressure on – Lockout alarm at start
20
Air pressure, fuel pressure on - Alarm lock at start
68
Air pressure, POC on – Alarm lockout at start
84
Air pressure, fuel pressure, POC on - Alarm lockout at start
4
#
Extraneous light
0
Extraneous light during start-up
1
Extraneous light during switch-off
2
Extraneous light during start-up – Lockout alarm at start
6
Extraneous light during start-up, air pressure - Alarm
lockout at start
18
Extraneous light during start-up, fuel pressure - Alarm
lockout at start
24
Extraneous light during start-up, air pressure, fuel pressure
- Alarm lockout at start
66
Extraneous light during start-up, POC – Alarm lockout at
start
70
Extraneous light during start-up, air pressure, POC - Alarm
lockout at start
82
Extraneous light during start-up, fuel pressure, POC -
Alarm lockout at start
86
Extraneous light during start-up, air pressure, fuel
pressure, poc - Alarm lockout at start
7
#
Loss of flame
0
Loss of flame
3
Flame loss (software version
V02.00)
3…255
Flame loss during TÜV test (flame loss test)
The diagnostics covers the period of time from the closure of the
fuel valves to the point the flame loss was detected (resolution
0.2 s
value 5 = 1 s
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......