20081825
10
GB
Technical description of the burner
4.4
Technical data
Tab. C
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at the test point of the pressure switch 5)(Fig. 5 on page 15) with zero pressure in the combustion chamber and at maximum burner
output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
power is measured with the “Free Field” method, as per EN 15036, and according to an accurate “Accuracy: Category 3”, as described by EN ISO
3746”.
Model
RLS 310/E MX
RLS 410/E MX
RLS 510/E MX
RLS 610/E MX
Type
1161T1
1162T1
1163T1
1164T1
Power
(1)
Delivery
(1)
min - max
kW
Kg/h
600/1200 - 3600
50/100 - 305
640/ 1500 - 4200
55/126 - 352
660/1800 - 5170
56/195 - 435
1000/2200 - 6155
110/185 - 516
Fuels
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
Light oil, max. viscosity at 20 °C: 6 mm
2
/s (1.5°E - 6 cSt)
Gas pressure at max. output
(2)
Gas: G20/G25
mbar
31.8/47.4
47.3/70.6
47.8/71.3
68.2/101.8
Operation
FS1: Intermittent (min. 1 stop in 24 hours)
Pump
Minimum output at 16.5 bar
Pressure range
kg/h
bar
TA 3
700
7/40
TA 4
930
7/40
TA 5
1270
7/30
Fuel temperature
°c max
140
Nozzles
number
1
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 50
Combustion air temperature
°C max
60
Noise level
(3)
Sound pressure
Sound power
dB(A)
78
89
80
91
82.5
93,5
85
96
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......