6.14.3 List of parameters
Parameter
No. of
elements
Unit of
measure-
ment
Modifica-
tion
Values interval
Degree of
precision
Predefined
setting
Access mode
No.
Description
Min.
Max.
000
INTERNAL PARAMETERS
050
Start backup/restore process via RDI21... / PC TOOL
(set the parameter to 1)
Index 0 = create backup
Index 1 = perform restore
Negative values indicate errors
2
-
Modification
-99
2
1
0; 0
Service mode
055
Burner identification number created from the backup
on RDI21...
1
-
Reading only
0
99999999
1
0
Service mode
056
ASN number created by the backup on RDI21...
8
-
Reading only
0
127
1
0
Service mode
057
Software Version created by the backup on RDI21...
1
-
Reading only
0x100
0xFFF9
1
0
Service mode
100
GENERAL PARAMETERS
102
Control box identification date
1
-
Reading only
0
255
1
Info mode
103
Control box identification number
1
-
Reading only
0
65535
1
Info mode
104
Identification number of the group of parameters set
1
-
Reading only
0
255
1
30
Info mode
105
Version of the group of parameters set
1
-
Reading only
0
0xFFFF
1
V 01.08
Info mode
107
Software version
1
-
Reading only
0
0xFFF9
1
V 03.30
Info mode
108
Software variation
1
-
Reading only
0
225
1
1
Info mode
111
ASN number to verify the ASN number created by the
backup on RDI 21…
8
-
Reading only
0
127
1
0
Service mode
113
Burner identification
1
-
Modification
0
99999999
1
Not defined
Info Mode
with password
Service Mode
121
Manual setting of output
Not defined = automatic operation
1
%
Modification /
zero setting
0%
100%
0.1%
Not defined
Info mode
123
Minimum output step position
Index 0: BACS output
Index 1: output of the external load regulator,
analogue.
Index 2: output of the external load regulator contacts.
3
%
Modification
0%
100%
0.1%
0%; 1%; 0%
Service mode
124
Beginning flame loss test (TÜV test)(define the
parameter at 1)(switch of flame loss fuel valves) A
negative value indicates an error (see code 150)
1
-
Modification
-6
1
1
0
Service mode
125
Frequency of main power supply
0 = 50 Hz
1 = 60 Hz
1
-
Modification
0
1
1
0
Service Mode
126
Brightness of display
1
%
Modification
0%
100%
1%
75%
Service Mode
128
Fuel meter: Led pulse valence
(led pulses / volumetric flow units)
1
-
Modification
0
400
0,01
0
Service Mode
130
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1,
then to 2
Answer 0: process successful
Answer -1: timeout of 1_2 - sequence
1
-
Modification
-5
2
1
0
Service Mode
133
Default output for TÜV test:
Not valid for TÜV test when output is activated
2,000 ..... 10,000 = low flame or first / second / third
stage
1
%
Modification /
zero setting
20%
100%
0.1%
Not defined
Service Mode
141
Remote management of control box
0 = off
1 = Modbus
2 = reserved
1
-
Modification
0
2
1
0
Service Mode
142
Standby time before a new attempt in event of com-
munication fault
Set values:
0 = not active
1 = .... 7200 s
1
s
Modification
0s
7200s
1s
120s
Service Mode
143
Reserved
1
-
Modification
1
8
1
1
Info Mode
144
Reserved
1
s
Modification
10s
60s
1s
30s
Service Mode
Summary of Contents for RLS 310/E MX
Page 2: ...Original instructions ...
Page 81: ...79 20081825 GB Appendix Electrical panel layout RLS 310 410 E MX 230 400V Direct Start Up ...
Page 84: ...20081825 82 GB Appendix Electrical panel layout ALL MODELS ...
Page 85: ...83 20081825 GB Appendix Electrical panel layout 0 ALL MODELS ...
Page 87: ...85 20081825 GB Appendix Electrical panel layout ALL MODELS ...
Page 94: ......
Page 95: ......