Family Aqua Condens 3.5 BIS
12
N°
PAR
PARAMETER DESCRIPTION
UNIT of
MEASUREMENT
MIN
MAX
DEFAULT
Factory set
PARAM
set
via T.A.C.
1
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
1
2
INSIGNIFICANT PARAMETER
10 (10kW*)
16 (16kW)
20 (20kW*)
26 (25kW)
30 (30kW*)
34 (35kW)
50 (50kW*)
70 (70kW*)
20
3
DEGREE OF BUILDING INSULATION
min
5
20
5
10
DOMESTIC WATER MODE
0 (OFF)
1 (instantaneous)
2 (not used)
3 (external storage tank with thermostat)
4 (external storage tank with probe)
5 (DS built-in storage tank)
6 (3S built-in storage tank)
6
11
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
60
12
MAXIMUM SET-POINT OF DHW STORAGE TANK
°C
40
80
60
13
STORAGE TANK OUTPUT TEMPERATURE
°C
50
85
80
14
STORAGE TANK DELTA
°C
0
10
5
20
HEATING MODE
0 (OFF)
1 (ON)
2 (REMOTE PANEL + AREA VALVES)
3 (BAG2)
4 (NOT USED)
5 (NOT USED)
6 (BAG2 MIX)
7 (NOT USED)
8 (NOT USED)
1
21
MAXIMUM HEATING SET-POINT
°C
40
80
80
22
MINIMUM HEATING SET-POINT
°C
20
39
20
23
MAXIMUM HEATING FAN SPEED
(Range Rated adjustment)
rpm
NG LPG
60(**) 59(**)
MAX
24
MINIMUM HEATING FAN SPEED
rpm
NG LPG
12(**) 19(**)
MIN
25
POSITIVE HEATING DIFFERENTIAL
°C
2
10
6
26
NEGATIVE HEATING DIFFERENTIAL
°C
2
10
6
28
REDUCED HEATING MAX. OUTPUT TIME
min
0
20
15
29
HEATING FORCES SHUT-OFF TIME
min
0
20
5
30
HEATING TIMER RESET FUNCTION
-
0 (NO)
1 (YES)
0
31
MAXIMUM HEATING SET-POINT 2CH (circuit 2)
°C
40
80
45
32
MINIMUM HEATING SET-POINT 2CH (circuit 2)
°C
20
39
25
35
POSITIVE HEATING DIFFERENTIAL 2CH (circuit 2)
°C
2
10
3
36
NEGATIVE HEATING DIFFERENTIAL 2CH (circuit 2)
°C
2
10
3
40
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
1
41
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
1
42
C.T.R.s FUNCTION
0 (OFF)
1 (AUTO)
1
43
HEATING MEMORY
0 (OFF)
1 (AUTO)
1
44
THERMOREGULATION FUNCTION
0 (OFF)
1 (AUTO)
1
45
THERMOREGULATION CURVE INCLINATION (OTC)
-
2.5
40
20
46
THERMOREGULATION FUNCTION 2CH
0 (OFF)
1 (AUTO)
1
47
THERMOREGULATION CURVE INCLINATION (OTC) 2CH
-
2.5
40
10
48
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
0
50
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
1
51
HEAT REQUEST TYPE CH1 (circuit 1)
-
0
1
0
52
HEAT REQUEST TYPE CH2 (circuit 2)
-
0
1
0
61
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
4
62
HEATING FUNCTION DELIVERY TEMP. (ON)
°C
0
10
6
63
STORAGE TANK ANTI-FREEZE FUNCTION
DELIVERY TEMP. (ON)
°C
0
10
6
65
EXTERNAL PROBE REACTIVITY
0 (VERY FAST)
255 (VERY SLOW)
20
85
SEMI-AUTOMATIC CHARGE
0 (DISABLED)
1 (ENABLED)
1