background image

Family Aqua Condens 3.5 BIS

12

ENGLISH

13

* The value is expressed on the display in rpm/100 (e.g. 3.700 = 37)
WARNING: certain default values may be different from those shown in the table, owing to the update level of the card.

86

PRESSURE OF SEMI-AUTOMATIC CHARGE (ON)

bar

0.4

1.0

0.6

87

PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING

0

90

VARIABLE SPEED PUMP

-

0

100

41

92

ENABLING OF POST-CIRCULATION 
FROM DHW TO HEATING

-

0

1

0

93

DURATION OF POST-CIRCULATION 
FROM DHW TO HEATING

-

1

255

5

94

PUMP IN CONTINUOUS MODE ON FIRST CIRCUIT

-

0

1

0

95

PUMP IN CONTINUOUS MODE ON SECOND CIRCUIT

-

0

1

0

4.5 

Setting the thermoregulation

Checking the external probe connection
After connecting the external probe to the boiler, you can use the 
INFO function to check, viewing the value of the external T° and 
checking the presence of the icon on the display, that the connection 
has been recognised by the adjustment card. It is normal for the val-
ues measured by the probe to be higher than those of a reference 
probe, immediately following installation.

THERMOREGULATION is activated and optimised by setting the fol-
lowing parameters:

PARAMETER

AVAILABLE IN THE 

PROGRAMMING ENVIRONMENT 

BUILDING TYPE

3

INSTALLATION AND 

CALIBRATION & SERVICE

MAXIMUM SET POINT HEATING

21

INSTALLATION

MINIMUM SET POINT HEATING

22

INSTALLATION

THERMOREGULATION 

FUNCTION ACTIVATION

44

INSTALLATION

CLIMATIC

COMPENSATION CURVE

45

INSTALLATION AND 

CALIBRATION & SERVICE

TYPE OF HEAT REQUEST

51

INSTALLATION

Thermoregulation function activation PARAMETER 44.
The connection of the external temperature probe, plus the value of 
PARAMETER 44 ON, allows the activation of the thermoregulation:
EXTERNAL PROBE CONNECTED and PARAMETER 44 = 1 (ON) 
The THERMOREGULATION is enabled. 
The INFO function allows you to see the value of the external probe, 
and to visualise the symbols associated with the THERMOREGULA-
TION function.

  Without the connection of the external probe, it is not possible 

to enable the THERMOREGULATION. 
In this case, PARAMETER 44 is ignored and its function is 
ineffective.

EXTERNAL PROBE CONNECTED and PARAMETER 44 = 0 (OFF) 
- in this case, the THERMOREGULATION is disabled, even though 
the external probe is connected.
The INFO function allows you to see the value of the external probe 
however. 
Symbols associated with the THERMOREGULATION function are 
not visualised.

PARAMETER 03 - Type of building
The adjustment system for processing the delivery temperature does 
not use the external temperature directly, but takes into account the 
thermal insulation of the building: in well-insulated buildings, external 
temperature variations have less effect on the ambient temperature 
compared with poorly insulated buildings. The level of thermal insu-
lation of the building is set via parameter 3, in compliance with the 
enclosed diagram.

New buildings

Old buildings

Hollow

Solid bricks

Stone

a

19

14

12

8

b

20

16

15

11

c

19

15

14

9

d

18

12

10

5

a

b

c

d

types of building

Maximum and minimum delivery temperature PARAMETERS 21 
and 22.
There are two parameters that allow to limit the delivery tempera-
ture produced automatically by the THERMOREGULATION function 
based on the type of system (see table).

System type

T° max

T° min

Cast iron radiators

80

60

Radiating panels

50

30

Fan coils

50

30

Floor

40

20

PARAMETER 21 determines the maximum delivery temperature 
(MAXIMUM HEATING SET-POINT).
PARAMETER 22 determines the MINIMUM DELIVERY TEMP. (MIN-
IMUM HEATING SET-POINT).

Choice of the climatic compensation curve PARAMETER 45.
The compensation curve for heating calculates the delivery tempera-
ture of the boiler based on particular parameters, optimising the op-
eration based on the outside temperature.
Therefore the choice of the curve depends on the minimum external 
design temperature (and therefore on the geographical location - see 
graph 1), and on the delivery design temperature (and therefore on 
the type of system).

Summary of Contents for FAMILY AQUA CONDENS 3.5 BIS

Page 1: ...FAMILY AQUA CONDENS 3 5 BIS EN INSTALLER AND USER MANUAL HU TELEP T SI S HASZN LATI K ZIK NYV...

Page 2: ...6 95 EK ir nyelv a kisfesz lts g berendez sekr l 2009 125 EK ir nyelv az energiafelhaszn l term kek k rnyezetbar t tervez s r l 2010 30 EU ir nyelv az energi val kapcsolatos term kek energia fogyaszt...

Page 3: ...of certain basic safety rules such as It is forbidden for children and unassisted unskilled people to use the boiler It is forbidden to activate electric devices or appliances such as switches househo...

Page 4: ...d the performances of which are indicated in the graph fig 1 2 The boiler is equipped with an anti blocking system which starts up an operation cycle after every 24 hours of stop with the mode selec t...

Page 5: ...est 3 3 Handling After unpacking handling of the boiler is done manually using the support frame fig 4 3 4 Boiler installation room The Family Aqua Condens 3 5 BIS boiler can be installed in vari ous...

Page 6: ...urn line G Gas SC Discharge manifold AF Cold water inlet AC Hot water outlet DISCHARGE MANIFOLD The discharge manifold collects condensate water any evacuation water from the safety valve and the syst...

Page 7: ...ilter of ade quate dimensions is recommended Once the installation is done check that the junctions carried out are sealed 3 11 Flue gas outlet and combustion air suction The Family Aqua Condens 3 5 B...

Page 8: ...he discharge manifold A for details refer to paragraph Discharge manifold drain the lowest points of the system Domestic hot water system unscrew the plug on the hose connection G connect a plastic pi...

Page 9: ...ise or fall The correction range is between 5 and 5 comfort levels These corrections are very important in the mid seasons when the value calculated by the curve may be too low and the room heating ti...

Page 10: ...essively turn it forward Undo by two turns the screw of the pressure test point upstream from the gas valve and connect the pressure gauge Power the boiler electrically by setting the main system swit...

Page 11: ...given within 10 seconds the value is not stored and the previous one is indicated again Setting the password The programming of the parameters is accessed by pressing the key and then pressing the ke...

Page 12: ...FFERENTIAL C 2 10 6 28 REDUCED HEATING MAX OUTPUT TIME min 0 20 15 29 HEATING FORCES SHUT OFF TIME min 0 20 5 30 HEATING TIMER RESET FUNCTION 0 NO 1 YES 0 31 MAXIMUM HEATING SET POINT 2CH circuit 2 C...

Page 13: ...th the THERMOREGULA TION function Without the connection of the external probe it is not possible to enable the THERMOREGULATION In this case PARAMETER 44 is ignored and its function is ineffective EX...

Page 14: ...mixed mode system To determine the curve for the mixed system acts as described for the parameter 45 To program the Max Heating Set Point use PARAMETER 31 To program the Min Heating Set Point use PAR...

Page 15: ...er is replaced 2 Display only of the RESET icon Press the key to restore operation If the boiler performs the fir ing procedure and resumes normal operation the stoppage can be attributed to a chance...

Page 16: ...e is activated every 24 h 4 8 Switching off for long periods The long term non use of the Family Aqua Condens 3 5 BIS boiler causes the execution of the following operations press The wording ENERGY F...

Page 17: ...the building only displayed if an external probe is connected 10 DHW mode do not modify this parameter 45 thermoregulation curve inclination only displayed if an external probe is connected 47 2CH the...

Page 18: ...ify the parameter value Turn the encoder to modify the maximum fan speed Confirm the new value by pressing ENTER The newly set value must be indicated on the adhesive label sup plied and will become t...

Page 19: ...mixer to the fan and remove it Unscrew the fixing screws of the plastic venturi tubes from the al uminium body Levering under the teeth DO NOT FORCE loosen the plastic venturi C and press from the op...

Page 20: ...the case of stubborn stains dampen the cloth with a mixture of 50 water and methylated spirit or with specific products Do not use fuels and or sponges soaked in abrasive solutions or powder detergent...

Page 21: ...tivate electric devices or appliances such as switches household appliances and so on if you notice a smell of fuel or unburned fuel In this case ventilate the room by opening the doors and windows cl...

Page 22: ...stop wait about 10 seconds before restoring the start up conditions D Adjusting the heating temperature To adjust the temperature of the outlet water press the heating tem perature adjustment key A Th...

Page 23: ...o digits will no longer show the temperature measured instan taneously by the probe but the temperature flashing previously set By rotating the encoder A you can raise or lower the temperature When 3...

Page 24: ...mory key Press the key to activate the Memory function the display will show the corresponding icon The Memory function activates smart heating electronics J Heating memory When the Memory key is acti...

Page 25: ...InFO list Info 1 Displays the outdoor temperature measured by the external probe only if an external probe is connected Info 2 Displays the system pressure value Info 3 Displays the set heating tempe...

Page 26: ...nt 3 2 Display only of the RESET icon Press the key to restore operation If the boiler performs the firing procedure and resumes normal operation the stoppage can be at tributed to a chance situation...

Page 27: ...d perform the fill ing operations described in the Filling and draining the systems chapter If the system pressure is sufficient 0 6 bar light blue field the fault is due to a lack of circulating wate...

Page 28: ...Flue gas capacity 46 561 45 286 Nm3 h Air excess index maximum output 1 304 1 376 Air excess index minimum output 1 235 1 376 CO2 at maximum minimum 9 00 9 50 10 00 10 00 CO S A at maximum minimum lo...

Page 29: ...space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficiency At rated heat output and high temperature regime P4 33 7 kW A...

Page 30: ...tse el ha olyan term keket haszn l amelyek t zel anyaggal rammal s v zzel m k dnek be kell tartani n h ny alapvet biztons gi szab lyt mint p ld ul Tilos a kaz nt gyerekeknek vagy k pzetlen szem lyekne...

Page 31: ...v laszt kapcsol A le ll sv d funkci csak akkor akt v ha a kaz n ramell t sa biztos tott Szigor an tilos a keringtet szivatty t v z n lk l zemeltetni 2 3 V ltoztathat sebess g keringtet szivatty A modu...

Page 32: ...lektromos v detts gi foka megfelel e a telep t si helyis g jellemz inek Amennyiben a kaz nt a leveg n l nagyobb fajs ly g zzal t pl lj k az elektromos r szeket a f ldt l 500 mm n l magasabbra kell elh...

Page 33: ...n id j r sf gg m don tudjon m k dni K LS H M RS KLET RZ KEL TELEP T SE S BEK T SE Az rz kel t a f tend p let k ls fal ra kell felszerelni betartva az al bbiakat Az p let leggyakrabban sz lnek kitett o...

Page 34: ...telep t si hely nek l gk r b l t rt nik amely helyis g e c lra alkalmas kell szell z ssel rendelkez kell legyen Az g sterm ket elvezet cs vek ha nem h szigeteltek potenci lis vesz lyforr st jelentene...

Page 35: ...ntjait Haszn lati v z rendszere csavarja ki a t ml tart n G l v kupakot csatlakoztasson egy m anyag cs vet a v zmeleg t G leereszt szelep nek t ml csatlakoz j ra ll tson a szelep leereszt k sz l k n k...

Page 36: ...stb vagy 1 2 stb sz m A f t si jelz sen vil g t vonalka fel vagy lemegy A korrig l s 5 s 5 komfortfokozat k z tt t rt nhet Ezek a korrekci k el s ut szezonban fontosak amikor a g rbe sz m tott rt ke...

Page 37: ...Emelje fel a m szerfalat s forgassa el refel Laz tsamegk tfordulattalag zszelepel ttl v nyom scsatlakoz csavarj t s csatlakoztassa a manom terhez Helyezze ram al a kaz nt a berendez s k zponti kapcsol...

Page 38: ...t rt nik v gleges t s a megadott rt k nem r gz l a mem ri ban s az el z rt k marad rv nyben Password jelsz be ll t sa A param terek programoz s ba a gombot lenyomva tartva majd a gombot kb 3 m sodper...

Page 39: ...LIS SEBESS GE ford perc MET N G Z PB G Z 12 19 MIN 25 POZIT V F T SI DIFFERENCI L C 2 10 6 26 NEGAT V F T SI DIFFERENCI L C 2 10 6 28 LECS KKENT F T SI MAX TELJES TM NY ID Z T SE min 0 20 15 29 F T S...

Page 40: ...dszer nem k zvetlen l haszn lja a k ls h m rs klet rz kel ltal m rt h m rs kleti rt ket hanem figyelembe veszi az p let h szigetel s nek jelleg t llapot t is a kell h szigetel ssel rendelkez p letekbe...

Page 41: ...i k rre OTC 2 CH 47 PARAM TER a kevert f t si k rre A kevert rendszer g rb j nek meghat roz s hoz a 45 param tern l le rtak szerint kell elj rni A F t si Max Set Point programoz s hoz haszn lja a 31 P...

Page 42: ...t Szerelje vissza a fedelet s ll tsa helyre a kaz n m k d s t MEGJEGYZ S a sz ml l t az els dleges h cser l minden egyes tiszt t sa vagy cser je ut n le kell null zni 2 Amikor csak a RESET ikon jelez...

Page 43: ...A kijelz n bekapcsol a villog ikon amely azt jelzi hogy a fagy sg tl funkci akt v Keringtet szivatty blokkol s g tl sa minden 24 r ban elindul egy zemel si ciklus 4 8 Kikapcsol s hosszabb id szakra A...

Page 44: ...a 45 id j r sk vet m d jellegg rb je csak akkor jelenik meg ha k ls h m rs klet rz kel van bek tve 47 id j r sk vet m d jellegg rb je a 2 f t si k rre csak akkor jelenik meg ha k ls h m rs klet rz kel...

Page 45: ...hozz f r shez Forgassa haszn lati melegv z h m rs klet szab lyoz gombj t a ventil tor maxim lis sebess g nek v ltoztat s hoz V gleges tse a be ll tott j rt ket az ENTER megnyom s val Az gy be ll tott...

Page 46: ...rozza ki a m anyag venturit az alum nium testhez r gz t csavarokat A fogak alatt VATOSAN NE ER LTESSE laz tsa meg a m anyag venturit C majd nyomja meg az ellent tes oldal n am g teljesen ki nem j n az...

Page 47: ...a rongyot 50 os v z denatur lt szesz kever kkel vagy a c lnak megfelel speci lis term kekkel Ne haszn ljon zemanyagot s vagy mar oldatban vagy por alak tiszt t szerbe mer tett szivacsokat Bels tiszt t...

Page 48: ...em lyeknek seg ts g n lk l haszn lniuk Tilos elektromos eszk z ket k sz l keket mint villanykapcsol k h ztart si g pek stb haszn lni vagy bekapcsolni ha f t anyag vagy g sterm k illatot rez Ebben az e...

Page 49: ...RESET gomb s a A rendelleness g le r s hoz s a bekapcsol si felt telek helyre ll t s hoz olvassa el a Kijelz s hibak dok pontot valamint a t bl zatot Biztons gi le ll st k vet en v rjon legal bb 10 m...

Page 50: ...tt pillanatban m rt rt k F Haszn lati v z h m rs klet nek be ll t sa A HMV h m rs klet nek be ll t s hoz nyomja meg a gombot A K t k dn l elt nik a szonda ltal m rt pillanatnyi h m rs klet s villogni...

Page 51: ...ajd 10 perc m lva 5 C kal n veli a mentett el remen h m rs kletet A Memory addig ism tli a ciklust am g a h m rs klet el nem ri a belt ri termoszt ton be ll tott rt ket vagy a maxim lisan megengedett...

Page 52: ...van ilyen N Rendelleness gek k djai s kijelz se Ha a rendszer f kapcsol j t felkapcsolva ll sba tette de a kaz n nem indul el akkor nincs ramell t s Ellen rizze hogy a k sz l k vill sdug ja ha van be...

Page 53: ...NEM PARAZITA L NG 11 NEM IGEN JB LI K S RLET FOLYAMATBAN T 12 NEM NEM G Z BEMENTI MIN NYOM S T 13 NEM IGEN G Z BEMENTI MIN NYOM S D 14 IGEN NEM TERMOSZT T HAT R RT K D 20 IGEN NEM F STG Z SZONDA R VID...

Page 54: ...ges h cser l tiszt t sa T zt r ventil tor s venturi tiszt t sa Ellen rizze a g z s v z biztons gi berendez seket Ellen rizze a g zhozamot s esetleges be ll t s t A f stg z cs s a huzat ellen rz se Az...

Page 55: ...jes tm ny f stg z t meg rama 1 498 2 740 g s Leveg mennyis ge 43 090 43 945 Nm3 h F stg z mennyis ge 46 561 45 286 Nm3 h Maxim lis teljes tm ny leveg t bblet mutat 1 304 1 376 Minim lis teljes tm ny l...

Page 56: ...kaz nok s kombin lt kaz nok eset ben hasznos h teljes tm ny Helyis gf t kaz nok s kombin lt kaz nok eset ben hat sfok M rt h teljes tm nyen s magas h m rs kleten P4 33 7 kW M rt h teljes tm nyen s mag...

Page 57: ...17 F stelemz s minta kupak HU Bejegyz si sz m HMV zemm d F t si zemm d Qn N vleges kapacit s Pn N vleges teljes tm ny Qm Minim lis kapacit s Pm Minim lis teljes tm ny IP V delmi fokozat Pmw Haszn lati...

Page 58: ...valve 21 Filling tap 22 System discharge valve 23 Pressure transducer A Heating return B Heating delivery C Hot water outlet D Cold water inlet HU Hidraulikus k r 1 F t si biztons gi szelep 2 Automati...

Page 59: ...justment to be carried out using the encoder c 1 3 5 9 8 7 6 4 2 HU Vez rl panel 1 Info GOMB Azt a funkci t aktiv lja amely lehet v teszi a kaz n bizonyos m k d si inform ci ihoz val hozz f r st 2 INT...

Page 60: ...water temperature the position in relation to the maximum and mini mum 16 Domestic hot water flame on indicates the burner is on follow ing a domestic hot water heat request HU Ikonok le r sa 1 Reset...

Page 61: ...Family Aqua Condens 3 5 BIS 61...

Page 62: ...age S E External probe M3 M6 Terminal board for external connections in High Voltage F External fuse 3 15A F HU T bbvezet kes bek t si rajz L N POLARIZ L S AJ NLOTT Blu K k Marrone Barna Nero Fekete R...

Page 63: ...F C1 C1 F B C D E HU Nagyfesz lts g csatlakoz sok A Kisfesz lts g csatlakoz sok B Nagyfesz lts g csatlakoz sok 230 V C Szobatermoszt t vagy kronotermoszt t C1 Szobatermoszt t D Id programoz E Szobater...

Page 64: ...3 2 3 4 3 6 3 8 4 0 4 2 4 4 4 6 4 8 5 0 5 2 5 4 5 6 5 8 6 0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Max Min PWM A A Standard modulating circulator curves 6m Soros modul ci s keringtet g r...