Family Aqua Condens 3.5 BIS
12
ENGLISH
13
* The value is expressed on the display in rpm/100 (e.g. 3.700 = 37)
WARNING: certain default values may be different from those shown in the table, owing to the update level of the card.
86
PRESSURE OF SEMI-AUTOMATIC CHARGE (ON)
bar
0.4
1.0
0.6
87
PARAMETER CAN NOT BE USED IN THIS MODEL, DO NOT MODIFY THE PROGRAMMING
0
90
VARIABLE SPEED PUMP
-
0
100
41
92
ENABLING OF POST-CIRCULATION
FROM DHW TO HEATING
-
0
1
0
93
DURATION OF POST-CIRCULATION
FROM DHW TO HEATING
-
1
255
5
94
PUMP IN CONTINUOUS MODE ON FIRST CIRCUIT
-
0
1
0
95
PUMP IN CONTINUOUS MODE ON SECOND CIRCUIT
-
0
1
0
4.5
Setting the thermoregulation
Checking the external probe connection
After connecting the external probe to the boiler, you can use the
INFO function to check, viewing the value of the external T° and
checking the presence of the icon on the display, that the connection
has been recognised by the adjustment card. It is normal for the val-
ues measured by the probe to be higher than those of a reference
probe, immediately following installation.
THERMOREGULATION is activated and optimised by setting the fol-
lowing parameters:
PARAMETER
AVAILABLE IN THE
PROGRAMMING ENVIRONMENT
BUILDING TYPE
3
INSTALLATION AND
CALIBRATION & SERVICE
MAXIMUM SET POINT HEATING
21
INSTALLATION
MINIMUM SET POINT HEATING
22
INSTALLATION
THERMOREGULATION
FUNCTION ACTIVATION
44
INSTALLATION
CLIMATIC
COMPENSATION CURVE
45
INSTALLATION AND
CALIBRATION & SERVICE
TYPE OF HEAT REQUEST
51
INSTALLATION
Thermoregulation function activation PARAMETER 44.
The connection of the external temperature probe, plus the value of
PARAMETER 44 ON, allows the activation of the thermoregulation:
EXTERNAL PROBE CONNECTED and PARAMETER 44 = 1 (ON)
The THERMOREGULATION is enabled.
The INFO function allows you to see the value of the external probe,
and to visualise the symbols associated with the THERMOREGULA-
TION function.
Without the connection of the external probe, it is not possible
to enable the THERMOREGULATION.
In this case, PARAMETER 44 is ignored and its function is
ineffective.
EXTERNAL PROBE CONNECTED and PARAMETER 44 = 0 (OFF)
- in this case, the THERMOREGULATION is disabled, even though
the external probe is connected.
The INFO function allows you to see the value of the external probe
however.
Symbols associated with the THERMOREGULATION function are
not visualised.
PARAMETER 03 - Type of building
The adjustment system for processing the delivery temperature does
not use the external temperature directly, but takes into account the
thermal insulation of the building: in well-insulated buildings, external
temperature variations have less effect on the ambient temperature
compared with poorly insulated buildings. The level of thermal insu-
lation of the building is set via parameter 3, in compliance with the
enclosed diagram.
New buildings
Old buildings
Hollow
Solid bricks
Stone
a
19
14
12
8
b
20
16
15
11
c
19
15
14
9
d
18
12
10
5
a
b
c
d
types of building
Maximum and minimum delivery temperature PARAMETERS 21
and 22.
There are two parameters that allow to limit the delivery tempera-
ture produced automatically by the THERMOREGULATION function
based on the type of system (see table).
System type
T° max
T° min
Cast iron radiators
80
60
Radiating panels
50
30
Fan coils
50
30
Floor
40
20
PARAMETER 21 determines the maximum delivery temperature
(MAXIMUM HEATING SET-POINT).
PARAMETER 22 determines the MINIMUM DELIVERY TEMP. (MIN-
IMUM HEATING SET-POINT).
Choice of the climatic compensation curve PARAMETER 45.
The compensation curve for heating calculates the delivery tempera-
ture of the boiler based on particular parameters, optimising the op-
eration based on the outside temperature.
Therefore the choice of the curve depends on the minimum external
design temperature (and therefore on the geographical location - see
graph 1), and on the delivery design temperature (and therefore on
the type of system).