Family Aqua Condens 3.5 BIS

8

The flue gases discharge pipe must be connected to the flue gases 
outlet.
For installation, follow the instructions supplied with the specific ac-
cessory kit for condensing boilers.

straight length of twin pipes ø 80mm

pressure drop

45° curve   90° curve

40+40 m

1 m

1,5m

  "Straight length" means without bends, drainage terminals or 

joints.

  The use of a longer pipe causes a loss of output of the boiler.

  It is compulsory to use specific pipes (see Riello catalogue).

  Make sure the flue gas discharge pipe is tilted 3° towards the 

boiler.

  The boiler automatically adapts the purging to the type of in-

stallation and the length of the pipes. Do not obstruct or choke 
the pipes in any way.

  For the indication of the maximum lengths of the single pipe, 

refer to the charts.

3.12 

POSSIBLE OUTLET CONFIGURATIONS (fig. 20)

B23P-B53P  Suction in room, with external outlet
C13-C13x 

  Concentric wall outlet. The pipes may also be split, 
but the outputs must be concentric or sufficiently 
close together to be subjected to similar wind condi-
tions

C23 

Concentric outlet in common smoke pipe (suction 
and discharge in the same pipe)

C33-C33x 

Concentric roof outlet. Outlets as for C13

C43 C43x 

 Discharge and suction in separate shared smoke 
pipes subject to similar wind conditions

C53-C53x 

 Separated discharge and suction on wall or roof, in 
areas with different pressure levels

C83 C83x 

 Outlet in single or shared smoke pipe and wall suc-
tion line.

C93-C93x 

 Discharge on roof (similar to C333) aand air suction 
from a single existing smoke pipe.

  Refer to the regulations in force.

System loading and emptying (fig. 21)

Once the hydraulic connections have been carried out, fill the system.

LOADING

Domestic hot water system:
-  open the cold water inlet tap to fill the storage tank
-  to check that the storage tank is full, open a hot water tap and wait 

for the water to exit.

Heating system:
-  make sure that the system drain valve (B) is closed
-  open the automatic air vent valve cap (C) by two or three turns
-  open the filling tap (H) until the pressure indicated by the water 

gauge (D) is between 1 and 1.5 bar (blue field).

-  open the manual bleed valve (E) and close it once the bleeding 

procedure is completed; if necessary, repeat this operation until no 
more air exits the valve (E)

-  once the filling operation of the system is finished, close the filling 

tap (H).

NOTE: the venting of the boiler takes place automatically via the two 
automatic bleed valves C and F.

NOTE: even if the boiler is fitted with an automatic filling device, the 
first filling operation must be carried out by turning the tap with the 
boiler off.

EMPTYING
-  Before starting emptying, switch off the electrical supply by turning 

off the system's main switch.

-  Close the cold water inlet tap.

Heating system:
-  close the shut-off devices of the heating system
-  open the automatic air vent valves (C - F)
-  manually loosen the system drain valve (B), keeping the elbow of 

the hose in position to prevent it slipping from its seat

-  the water is discharged through the discharge manifold (A) - for 

details refer to paragraph "Discharge manifold".

-  drain the lowest points of the system.

Domestic hot water system:
-  unscrew the plug on the hose connection (G)
-  connect a plastic pipe to the hose connection of the storage tank 

discharge valve (G)

-  release the discharge device of the valve
-  open the hot and cold water taps of the device
-  drain the lowest points of the system.

  The discharge manifold (A) must be connected via a rubber pipe 

to an appropriate collection and evacuation system in the white 
water discharge drain in compliance with current regulations. 
The outer diameter of the manifold is 20 mm: it is therefore ad-
visable to use a rubber pipe Ø18-19 mm closed with a suita-
ble clamp (not provided). The manufacturer is not liable for any 
damage resulting from the failure to channel the condensate.

Suggestions for the correct elimination of air from the heating 
circuit and from the boiler 

(fig.22).

During the initial installation phase, or in the event of extraordinary 
maintenance, you are advised to perform the following sequence of 
operations:
1.  With a CH11 wrench, open the manual air vent valve: Connect 

the tube (supplied with the boiler) to the valve, so the water can 
be drained into an external container.

2.  Turn on the system filler tap on the DHW, and wait until water 

begins to seep out of the valve.

3.  Switch on the electricity supply to the boiler, leaving the gas tap 

turned off.

4.  Activate a heat request via the ambient thermostat or the remote 

control panel, so that the 3-way valve goes into heating mode.

5.  Activate a domestic water request by either turning on a tap (in 

the case of instantaneous boilers) or via the storage tank ther-
mostat (for heating-only boilers connected to an external stor-
age tank) for 30” every minute so the 3-way valve passes from 
heating to domestic water and vice versa about 10 times. In this 
situation, the boiler will go into alarm mode due to the absence of 
gas, so it must be reset every time this happens).

6.  Carry on with the sequence until only water leaks out of the man-

ual air vent valve, and the air flow has stopped; now close the 
manual air vent valve.

7.  Check the system pressure level is correct (the ideal level is 1 bar).
8.  Turn off the system filling tap on the DHW.
9.  Turn on the gas tap and ignite the boiler.

4 -  COMMISSIONING AND MAINTENANCE

4.1 

First commissioning preparation

Before the ignition and the functional testing of the Family Aqua 
Condens 3.5 BIS 
boiler, it is necessary to:
-  check that the system fuel and water supply taps are open
-  check that the gas type and the power supply pressure are those 

for which the boiler is designed

-  check that the deaerator cap is open
-  check on the display that the pressure of the water circuit when 

cold is between 1 bar and 1.5 bar and that the circuit is vented

-  check that the pre-loading of the expansion tank is adequate (see 

the Technical data table)

-  check that the electrical connections have been carried out cor-

rectly

-  check that the combustion product outlet and air suction pipes 

were adequately realised

-  check that the circulator turns freely; undo the inspection screw 

and check with a flat screwdriver that the rotor shaft moves without 
hindrances.

Summary of Contents for FAMILY AQUA CONDENS 3.5 BIS

Page 1: ...FAMILY AQUA CONDENS 3 5 BIS EN INSTALLER AND USER MANUAL HU TELEP T SI S HASZN LATI K ZIK NYV...

Page 2: ...6 95 EK ir nyelv a kisfesz lts g berendez sekr l 2009 125 EK ir nyelv az energiafelhaszn l term kek k rnyezetbar t tervez s r l 2010 30 EU ir nyelv az energi val kapcsolatos term kek energia fogyaszt...

Page 3: ...of certain basic safety rules such as It is forbidden for children and unassisted unskilled people to use the boiler It is forbidden to activate electric devices or appliances such as switches househo...

Page 4: ...d the performances of which are indicated in the graph fig 1 2 The boiler is equipped with an anti blocking system which starts up an operation cycle after every 24 hours of stop with the mode selec t...

Page 5: ...est 3 3 Handling After unpacking handling of the boiler is done manually using the support frame fig 4 3 4 Boiler installation room The Family Aqua Condens 3 5 BIS boiler can be installed in vari ous...

Page 6: ...urn line G Gas SC Discharge manifold AF Cold water inlet AC Hot water outlet DISCHARGE MANIFOLD The discharge manifold collects condensate water any evacuation water from the safety valve and the syst...

Page 7: ...ilter of ade quate dimensions is recommended Once the installation is done check that the junctions carried out are sealed 3 11 Flue gas outlet and combustion air suction The Family Aqua Condens 3 5 B...

Page 8: ...he discharge manifold A for details refer to paragraph Discharge manifold drain the lowest points of the system Domestic hot water system unscrew the plug on the hose connection G connect a plastic pi...

Page 9: ...ise or fall The correction range is between 5 and 5 comfort levels These corrections are very important in the mid seasons when the value calculated by the curve may be too low and the room heating ti...

Page 10: ...essively turn it forward Undo by two turns the screw of the pressure test point upstream from the gas valve and connect the pressure gauge Power the boiler electrically by setting the main system swit...

Page 11: ...given within 10 seconds the value is not stored and the previous one is indicated again Setting the password The programming of the parameters is accessed by pressing the key and then pressing the ke...

Page 12: ...FFERENTIAL C 2 10 6 28 REDUCED HEATING MAX OUTPUT TIME min 0 20 15 29 HEATING FORCES SHUT OFF TIME min 0 20 5 30 HEATING TIMER RESET FUNCTION 0 NO 1 YES 0 31 MAXIMUM HEATING SET POINT 2CH circuit 2 C...

Page 13: ...th the THERMOREGULA TION function Without the connection of the external probe it is not possible to enable the THERMOREGULATION In this case PARAMETER 44 is ignored and its function is ineffective EX...

Page 14: ...mixed mode system To determine the curve for the mixed system acts as described for the parameter 45 To program the Max Heating Set Point use PARAMETER 31 To program the Min Heating Set Point use PAR...

Page 15: ...er is replaced 2 Display only of the RESET icon Press the key to restore operation If the boiler performs the fir ing procedure and resumes normal operation the stoppage can be attributed to a chance...

Page 16: ...e is activated every 24 h 4 8 Switching off for long periods The long term non use of the Family Aqua Condens 3 5 BIS boiler causes the execution of the following operations press The wording ENERGY F...

Page 17: ...the building only displayed if an external probe is connected 10 DHW mode do not modify this parameter 45 thermoregulation curve inclination only displayed if an external probe is connected 47 2CH the...

Page 18: ...ify the parameter value Turn the encoder to modify the maximum fan speed Confirm the new value by pressing ENTER The newly set value must be indicated on the adhesive label sup plied and will become t...

Page 19: ...mixer to the fan and remove it Unscrew the fixing screws of the plastic venturi tubes from the al uminium body Levering under the teeth DO NOT FORCE loosen the plastic venturi C and press from the op...

Page 20: ...the case of stubborn stains dampen the cloth with a mixture of 50 water and methylated spirit or with specific products Do not use fuels and or sponges soaked in abrasive solutions or powder detergent...

Page 21: ...tivate electric devices or appliances such as switches household appliances and so on if you notice a smell of fuel or unburned fuel In this case ventilate the room by opening the doors and windows cl...

Page 22: ...stop wait about 10 seconds before restoring the start up conditions D Adjusting the heating temperature To adjust the temperature of the outlet water press the heating tem perature adjustment key A Th...

Page 23: ...o digits will no longer show the temperature measured instan taneously by the probe but the temperature flashing previously set By rotating the encoder A you can raise or lower the temperature When 3...

Page 24: ...mory key Press the key to activate the Memory function the display will show the corresponding icon The Memory function activates smart heating electronics J Heating memory When the Memory key is acti...

Page 25: ...InFO list Info 1 Displays the outdoor temperature measured by the external probe only if an external probe is connected Info 2 Displays the system pressure value Info 3 Displays the set heating tempe...

Page 26: ...nt 3 2 Display only of the RESET icon Press the key to restore operation If the boiler performs the firing procedure and resumes normal operation the stoppage can be at tributed to a chance situation...

Page 27: ...d perform the fill ing operations described in the Filling and draining the systems chapter If the system pressure is sufficient 0 6 bar light blue field the fault is due to a lack of circulating wate...

Page 28: ...Flue gas capacity 46 561 45 286 Nm3 h Air excess index maximum output 1 304 1 376 Air excess index minimum output 1 235 1 376 CO2 at maximum minimum 9 00 9 50 10 00 10 00 CO S A at maximum minimum lo...

Page 29: ...space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficiency At rated heat output and high temperature regime P4 33 7 kW A...

Page 30: ...tse el ha olyan term keket haszn l amelyek t zel anyaggal rammal s v zzel m k dnek be kell tartani n h ny alapvet biztons gi szab lyt mint p ld ul Tilos a kaz nt gyerekeknek vagy k pzetlen szem lyekne...

Page 31: ...v laszt kapcsol A le ll sv d funkci csak akkor akt v ha a kaz n ramell t sa biztos tott Szigor an tilos a keringtet szivatty t v z n lk l zemeltetni 2 3 V ltoztathat sebess g keringtet szivatty A modu...

Page 32: ...lektromos v detts gi foka megfelel e a telep t si helyis g jellemz inek Amennyiben a kaz nt a leveg n l nagyobb fajs ly g zzal t pl lj k az elektromos r szeket a f ldt l 500 mm n l magasabbra kell elh...

Page 33: ...n id j r sf gg m don tudjon m k dni K LS H M RS KLET RZ KEL TELEP T SE S BEK T SE Az rz kel t a f tend p let k ls fal ra kell felszerelni betartva az al bbiakat Az p let leggyakrabban sz lnek kitett o...

Page 34: ...telep t si hely nek l gk r b l t rt nik amely helyis g e c lra alkalmas kell szell z ssel rendelkez kell legyen Az g sterm ket elvezet cs vek ha nem h szigeteltek potenci lis vesz lyforr st jelentene...

Page 35: ...ntjait Haszn lati v z rendszere csavarja ki a t ml tart n G l v kupakot csatlakoztasson egy m anyag cs vet a v zmeleg t G leereszt szelep nek t ml csatlakoz j ra ll tson a szelep leereszt k sz l k n k...

Page 36: ...stb vagy 1 2 stb sz m A f t si jelz sen vil g t vonalka fel vagy lemegy A korrig l s 5 s 5 komfortfokozat k z tt t rt nhet Ezek a korrekci k el s ut szezonban fontosak amikor a g rbe sz m tott rt ke...

Page 37: ...Emelje fel a m szerfalat s forgassa el refel Laz tsamegk tfordulattalag zszelepel ttl v nyom scsatlakoz csavarj t s csatlakoztassa a manom terhez Helyezze ram al a kaz nt a berendez s k zponti kapcsol...

Page 38: ...t rt nik v gleges t s a megadott rt k nem r gz l a mem ri ban s az el z rt k marad rv nyben Password jelsz be ll t sa A param terek programoz s ba a gombot lenyomva tartva majd a gombot kb 3 m sodper...

Page 39: ...LIS SEBESS GE ford perc MET N G Z PB G Z 12 19 MIN 25 POZIT V F T SI DIFFERENCI L C 2 10 6 26 NEGAT V F T SI DIFFERENCI L C 2 10 6 28 LECS KKENT F T SI MAX TELJES TM NY ID Z T SE min 0 20 15 29 F T S...

Page 40: ...dszer nem k zvetlen l haszn lja a k ls h m rs klet rz kel ltal m rt h m rs kleti rt ket hanem figyelembe veszi az p let h szigetel s nek jelleg t llapot t is a kell h szigetel ssel rendelkez p letekbe...

Page 41: ...i k rre OTC 2 CH 47 PARAM TER a kevert f t si k rre A kevert rendszer g rb j nek meghat roz s hoz a 45 param tern l le rtak szerint kell elj rni A F t si Max Set Point programoz s hoz haszn lja a 31 P...

Page 42: ...t Szerelje vissza a fedelet s ll tsa helyre a kaz n m k d s t MEGJEGYZ S a sz ml l t az els dleges h cser l minden egyes tiszt t sa vagy cser je ut n le kell null zni 2 Amikor csak a RESET ikon jelez...

Page 43: ...A kijelz n bekapcsol a villog ikon amely azt jelzi hogy a fagy sg tl funkci akt v Keringtet szivatty blokkol s g tl sa minden 24 r ban elindul egy zemel si ciklus 4 8 Kikapcsol s hosszabb id szakra A...

Page 44: ...a 45 id j r sk vet m d jellegg rb je csak akkor jelenik meg ha k ls h m rs klet rz kel van bek tve 47 id j r sk vet m d jellegg rb je a 2 f t si k rre csak akkor jelenik meg ha k ls h m rs klet rz kel...

Page 45: ...hozz f r shez Forgassa haszn lati melegv z h m rs klet szab lyoz gombj t a ventil tor maxim lis sebess g nek v ltoztat s hoz V gleges tse a be ll tott j rt ket az ENTER megnyom s val Az gy be ll tott...

Page 46: ...rozza ki a m anyag venturit az alum nium testhez r gz t csavarokat A fogak alatt VATOSAN NE ER LTESSE laz tsa meg a m anyag venturit C majd nyomja meg az ellent tes oldal n am g teljesen ki nem j n az...

Page 47: ...a rongyot 50 os v z denatur lt szesz kever kkel vagy a c lnak megfelel speci lis term kekkel Ne haszn ljon zemanyagot s vagy mar oldatban vagy por alak tiszt t szerbe mer tett szivacsokat Bels tiszt t...

Page 48: ...em lyeknek seg ts g n lk l haszn lniuk Tilos elektromos eszk z ket k sz l keket mint villanykapcsol k h ztart si g pek stb haszn lni vagy bekapcsolni ha f t anyag vagy g sterm k illatot rez Ebben az e...

Page 49: ...RESET gomb s a A rendelleness g le r s hoz s a bekapcsol si felt telek helyre ll t s hoz olvassa el a Kijelz s hibak dok pontot valamint a t bl zatot Biztons gi le ll st k vet en v rjon legal bb 10 m...

Page 50: ...tt pillanatban m rt rt k F Haszn lati v z h m rs klet nek be ll t sa A HMV h m rs klet nek be ll t s hoz nyomja meg a gombot A K t k dn l elt nik a szonda ltal m rt pillanatnyi h m rs klet s villogni...

Page 51: ...ajd 10 perc m lva 5 C kal n veli a mentett el remen h m rs kletet A Memory addig ism tli a ciklust am g a h m rs klet el nem ri a belt ri termoszt ton be ll tott rt ket vagy a maxim lisan megengedett...

Page 52: ...van ilyen N Rendelleness gek k djai s kijelz se Ha a rendszer f kapcsol j t felkapcsolva ll sba tette de a kaz n nem indul el akkor nincs ramell t s Ellen rizze hogy a k sz l k vill sdug ja ha van be...

Page 53: ...NEM PARAZITA L NG 11 NEM IGEN JB LI K S RLET FOLYAMATBAN T 12 NEM NEM G Z BEMENTI MIN NYOM S T 13 NEM IGEN G Z BEMENTI MIN NYOM S D 14 IGEN NEM TERMOSZT T HAT R RT K D 20 IGEN NEM F STG Z SZONDA R VID...

Page 54: ...ges h cser l tiszt t sa T zt r ventil tor s venturi tiszt t sa Ellen rizze a g z s v z biztons gi berendez seket Ellen rizze a g zhozamot s esetleges be ll t s t A f stg z cs s a huzat ellen rz se Az...

Page 55: ...jes tm ny f stg z t meg rama 1 498 2 740 g s Leveg mennyis ge 43 090 43 945 Nm3 h F stg z mennyis ge 46 561 45 286 Nm3 h Maxim lis teljes tm ny leveg t bblet mutat 1 304 1 376 Minim lis teljes tm ny l...

Page 56: ...kaz nok s kombin lt kaz nok eset ben hasznos h teljes tm ny Helyis gf t kaz nok s kombin lt kaz nok eset ben hat sfok M rt h teljes tm nyen s magas h m rs kleten P4 33 7 kW M rt h teljes tm nyen s mag...

Page 57: ...17 F stelemz s minta kupak HU Bejegyz si sz m HMV zemm d F t si zemm d Qn N vleges kapacit s Pn N vleges teljes tm ny Qm Minim lis kapacit s Pm Minim lis teljes tm ny IP V delmi fokozat Pmw Haszn lati...

Page 58: ...valve 21 Filling tap 22 System discharge valve 23 Pressure transducer A Heating return B Heating delivery C Hot water outlet D Cold water inlet HU Hidraulikus k r 1 F t si biztons gi szelep 2 Automati...

Page 59: ...justment to be carried out using the encoder c 1 3 5 9 8 7 6 4 2 HU Vez rl panel 1 Info GOMB Azt a funkci t aktiv lja amely lehet v teszi a kaz n bizonyos m k d si inform ci ihoz val hozz f r st 2 INT...

Page 60: ...water temperature the position in relation to the maximum and mini mum 16 Domestic hot water flame on indicates the burner is on follow ing a domestic hot water heat request HU Ikonok le r sa 1 Reset...

Page 61: ...Family Aqua Condens 3 5 BIS 61...

Page 62: ...age S E External probe M3 M6 Terminal board for external connections in High Voltage F External fuse 3 15A F HU T bbvezet kes bek t si rajz L N POLARIZ L S AJ NLOTT Blu K k Marrone Barna Nero Fekete R...

Page 63: ...F C1 C1 F B C D E HU Nagyfesz lts g csatlakoz sok A Kisfesz lts g csatlakoz sok B Nagyfesz lts g csatlakoz sok 230 V C Szobatermoszt t vagy kronotermoszt t C1 Szobatermoszt t D Id programoz E Szobater...

Page 64: ...3 2 3 4 3 6 3 8 4 0 4 2 4 4 4 6 4 8 5 0 5 2 5 4 5 6 5 8 6 0 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 Max Min PWM A A Standard modulating circulator curves 6m Soros modul ci s keringtet g r...

Page 65: ...Family Aqua Condens 3 5 BIS 65 8 7 6 3 4 piastra di supporto dima di premontaggio A B C EN A Mounting plate B Pre assembly template HU A Al t maszt lemez B El szerel sablon A B 5 50 mm 50 mm 200 mm...

Page 66: ...5 EN A Discharge manifold HU A kivezet cs 17 P2 separatore idraulico circolatore di caldaia caldaia circolatore supplementare A B C D EN A Boiler B Boiler circulator C Supplementary circulator D Hydra...

Page 67: ...ength of discharge pipe m B Length of suction pipe m HU A Kivezet cs hossza m B Besz v cs hossza m B A 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90...

Page 68: ...Cod 20117081 03 06 Ed 0...

Reviews: