Cable glands
The RW motor-gearbox has (installed) cable glands M20x1.5 mm and/or M16x1.5 mm to put
through the motor connections (EM) and the limit-switch cables (RLS/RSU).
The conditions and starting points that follow are applicable:
• Always put only
one cable
through
one cable gland
.
•
Use a cable with a conductor-diameter of
Ø6.0–12.0 mm
and a tightening torque of
5.0 Nm
for
cable glands
M20x1.5 mm
.
Use a cable with a conductor-diameter of
Ø5.0–10.0 mm
and a tightening torque of
2.5 Nm
for
cable glands
M16x1.5 mm
.
•
Make sure that water
flows away
from the cable glands (cable routing: make loops if necessary).
Obey the procedure that follows:
❶ Loosen the cable gland.
❷ Remove the sealing plug
*
.
❸ Put the cable through the cable gland.
❹ Tighten the cable glands with the correct tool and tightening torque.
*
If your decision is not to use this cable gland, make sure to put the sealing plug back. Tighten the
cable gland with the correct tool and tightening torque
!
Make sure that all openings are correctly sealed with cable glands
or with initially installed blind plugs. This prevents problems with
moisture and/or the IP protection rating.
Ø6.0–12.0 mm
M20x1.5/M16x1.5
- 5 Nm
- 2.5 Nm
Ø5.0–10.0 mm