Rich Electric Co. “SuperCombi” User Manual V7.19 Copyright 2009
Page 92
B4-02: 2-3 Phase Master
Main Menu>Programming>ENT>General>ENT>2-3 Phase>ENT
z
In a multi-phase system, there is always one (and only one) master. The SuperCombi® for other
phases are called followers.
z
Use this setting to designate one of the SuperCombi® is master. If this parameter is set
(B4-02=0), the SuperCombi® is a follower.
Setting Function
B4-02=0
(Initial setting)
2-3 Phase connection system is called Follower
B4-02=1
2-3 Phase connection system is called Master
B4-03: 2-3 Phase Type
Main Menu>Programming>ENT>General>ENT>2-3 Phase>ENT
z
Use constant B4-03 to determine the kind of multi-phase required.
Setting Function
B4-03=0
(Initial setting)
3 Phase type:
Three SuperCombi® are required.
Output is 3-phase with 120
°
phase shift.
B4-03=1
Split Phase 180
°
Type:
Two SuperCombi® are required.
Output is 2-phase with phase 180
°
shift
B4-03=2
Two Leg 3 Phase 120
°
Type:
Two SuperCombi® are required.
Output is 2-phase of a normal 3-phase system so two phases
with 120
°
phase shift.