D1-09: Battery Safe Mode “Stop After 10Hr Bulk”
Main Menu>Programming>ENT>Charger>ENT
z
The Battery safe setting is designed to shut down the charger when the bulk charging phase lasts
more than 10 hours, this can be indication that a battery cell is damaged.
z
The absorption voltage (or the 14.4V for battery when Battery Safe (D1-02=3) mode is used)
will never be reached in that case and the other cells will be over-charged resulting in the
production of an explosive gas.
z
Therefore, the charger is disabled if the bulk phase lasts more than 10 hours.
z
This setting can be disabled because it does not always indicate a problem when the bulk phase
lasts very long. The charge current can be very low due to limited AC input current and/or AC
loads. Also, DC loads can “steal away” part of the charge current. In that case, the bulk phase
will need more time to complete and this setting must be disabled.
※
Note: When this setting is disabled, there is no safety check against over-charging.
Setting Function
D1-09=0
Stop After 10Hr Bulk setting is disabled
D1-09=1
(Initial setting)
Stop After 10Hr Bulk setting is enabled
D1-10: Equalize Mode Select (Storage Mode Select)
Main Menu>Programming>ENT>Charger>ENT
z
This setting is used for enabling/disabling the Equalize Mode.
Setting Function
D1-10=0
Equalize mode is disabled
D1-10=1
(Initial setting)
Equalize mode is enabled
Summary of Contents for Invertek SuperCombi SC-1500-12X
Page 1: ......
Page 2: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 2...
Page 9: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 9 Layout...
Page 125: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 125 Chapter 8 Constants list...
Page 155: ...Rich Electric Co SuperCombi User Manual V7 19 Copyright 2009 Page 155 NOTES...