Distance Relay Setting Examples
GARD 8000 Distance Relay
RFL Electronics Inc.
Description Range
Units
Step
Actual
51P-1 Time Dial
Set the time dial for the selected curve
0.05 - 10
-
0.01
1
51P-1 Time Delay
Sets the minimum time delay for the curves with Time Limit (TL)
for the phase timeovercurrent element, step 1
0.05 - 300
s
0.01
0.05
51P-1 Torque Control Direction
Directional control of phase timeovercurrent element, step 1
NO
Forward
Reverse - 1
NO
51P-1 Torque Control Type
Selection to use directional element or Zone 2 for torque control
of the phase timeovercurrent element, step 1
67P
Z2
- 1
67P
Enable timeovercurrent phase (51P-2)
Enable phase timeovercurrent element, step 2
No - Yes
-
1
No
51P-2 Pick-Up
Pick-up level for phase timeovercurrent element, step 2
0.10 - 125
A
0.01
2
51P-2 Time Curve
Sets the time/current characteristic for phase timeovercurrent
element, step 2
(see time
curve
selection
below) - 1
Definite
Time
51P-2 Time Dial
Set the time dial for the selected curve
0.05 - 10
-
0.01
1
51P-2 Time Delay
Sets the minimum time delay for the curves with Time Limit (TL)
for the phase timeovercurrent element, step 2
0.05 - 300
s
0.01
0.05
51P-2 Torque Control Direction
Directional control of phase timeovercurrent element, step 2
NO
Forward
Reverse
- 1
NO
51P-2 Torque Control Type
Selection to use directional element or Zone 2 for torque control
of the phase timeovercurrent element, step 2
67P
Z2 -
1 67P
Enable timeovercurrent phase (51P-3)
Enable phase timeovercurrent element, step 3
No - Yes
-
1
No
51P-3 Pick-Up
Pick-up level for phase timeovercurrent element, step 3
0.10 - 125
A
0.01
2
51P-3 Time Curve
Sets the time/current characteristic for phase timeovercurrent
element, step 3
(see time
curve
selection
below) - 1
Definite
Time
51P-3 Time Dial
Sets the time dial for the selected curve
0.05 - 10
-
0.01
1
51P-3 Time Delay
Sets the minimum time delay for the curves with Time Limit (TL)
for the phase timeovercurrent element, step 3
0.05 - 300
s
0.01
0.05
51P-3 Torque Control Direction
Directional control of phase timeovercurrent element, step 3
NO
Forward
Reverse - 1
NO
51P-3 Torque Control Type
Selection to use directional element or Zone 2 for torque control
of the phase timeovercurrent element, step 3
67P
Z2 -
1 67P
August 1, 2009
8-33
973.334.3100