Sequence of Events Reports and Fault Recording
GARD 8000 Distance Relay
RFL Electronics Inc.
10.2.1
SEQUENCE OF EVENTS
100 SOE’s are recorded in the Distance SOE, with the oldest numbered as #1 and the newest as #100.
The record is accessed by selecting the distance relay module on the main status screen, and selecting
Distance Sequence of Events. The events are time tagged from the system clock with a resolution of
1 ms.
The distance elements that trigger an SOE record are defined in the ‘SOE Mask’ settings.
Figure 10-6. Distance SOE screen
March 1, 2009
10-6