Distance Relay Logic Programming
GARD 8000 Distance Relay
RFL Electronics Inc.
11.3.2
PUSHBUTTON OPERATIONS
The GARD can be supplied with an optional touch screen (TSD) user interface, and one of these
screens displays soft buttons for pre-defined operations. The factory default logic configures 4
pushbuttons to operate:
•
Reset oscillography
•
Block Trip (Cut-out)
•
Manual Close (Close CB)
•
Open CB
The Push Button Interface can be configured from the GARD System webpages, and also programmed
to operate on other virtual inputs. Please refer to System Logic Programming Manual.
11.3.3
DEFAULT INPUT PROGRAMMING
The following signals are supplied as standard. Note that any physical input can be connected to any
number of virtual inputs via the input mapping pages.
No Signal
Option
logic
1 RESET
OSC
PBI
2 BLOCK
TRIP
PBI
3 MANUAL
CLOSE
PBI
4 OPEN
CB
PBI
5
52 B
Inverter /dual-single CB
6 89
B
Inverter
7 TRIG
OSC
8
21 PILOT BLOCK
9
67 PILOT BLOCK
10 21
CARRIER
RECEIVE
11
21 LOSS OF GUARD
12 67
CARRIER
RECEIVE
13
67 LOSS OF GUARD
14 EXTERNAL
TRIP
15 EXTERNAL
RECLOSE
INITIATE
16
EXTERNAL LOP BLOCK
17
RECLOSE EXTERNAL BLOCK
18 RECLOSE
EXTERNAL
UNBLOCK
19
RECLOSE MANUAL BLOCK
20 RECLOSE
MANUAL
UNBLOCK
21 CLOSE
TRIP
CONTACT
22 EXTERNAL
50BF
START
23
EXTERNAL 50BF-G START
24 EXTERNAL
POLE
DISCORDANCE
25
EXTERNAL SYNCH CHECK
26 INVERT
DIRECTION
27 67G
INHIBIT
March 1, 2009
11-2
973.334.3100