Distance Relay Settings
GARD 8000 Distance Relay
RFL Electronics Inc.
Description Range
Units
Step
Default
Start Time
Recloser start timer. If this time expires before the recluse initiate signal
resets, the circuit breaker opens and the TRIP signal resets, the recloser
goes into lock-out.
0.07 - 0.6
s
0.01
0.2
Zone 1 RI
Enable reclose initiate from Zone 1 trips
Disable -
Enable
- 1 Disable
Zone 2 RI
Enable reclose initiate from Zone 2 trips
Disable -
Enable
- 1 Disable
Zone 3 RI
Enable reclose initiate from Zone 3 trips
Disable -
Enable - 1 Disable
Zone 4 RI
Enable reclose initiate from Zone 4 trips
Disable -
Enable - 1 Disable
50P-1 RI
Enable reclose initiate from phase instantaneous overcurrent trips, Step
1
Disable -
Enable - 1 Disable
50P-2 RI
Enable reclose initiate from phase instantaneous overcurrent trips, Step
2
Disable -
Enable - 1 Disable
50P-3 RI
Enable reclose initiate from phase instantaneous overcurrent trips, Step
3
Disable -
Enable - 1 Disable
51P-1 RI
Enable reclose initiate from phase timeovercurrent trips, Step 1
Disable -
Enable - 1 Disable
51P-2 RI
Enable reclose initiate from phase timeovercurrent trips, Step 2
Disable -
Enable - 1 Disable
51P-3 RI
Enable reclose initiate from phase timeovercurrent trips, Step 3
Disable -
Enable
- 1 Disable
50G-1 RI
Enable reclose initiate from ground instantaneous overcurrent trips, Step
1
Disable -
Enable - 1 Disable
50G-2 RI
Enable reclose initiate from ground instantaneous overcurrent trips, Step
2
Disable -
Enable
- 1 Disable
50G-3 RI
Enable reclose initiate from ground instantaneous overcurrent trips, Step
3
Disable -
Enable - 1 Disable
51G-1 RI
Enable reclose initiate from ground timeovercurrent trips, Step 1
Disable -
Enable - 1 Disable
51G-2 RI
Enable reclose initiate from ground timeovercurrent trips, Step 2
Disable -
Enable
- 1 Disable
51G-3 RI
Enable reclose initiate from ground timeovercurrent trips, Step 3
Disable -
Enable
- 1 Disable
50Q-1 RI
Enable reclose initiate from negative sequence instantaneous
overcurrent trips, Step 1
Disable -
Enable - 1 Disable
50Q-2 RI
Enable reclose initiate from negative sequence instantaneous
overcurrent trips, Step 2
Disable -
Enable - 1 Disable
50Q-3 RI
Enable reclose initiate from negative sequence instantaneous
overcurrent trips, Step 3
Disable -
Enable - 1 Disable
51Q-1 RI
Enable reclose initiate from negative sequence time overcurrent
trips, Step 1
Disable -
Enable - 1 Disable
July 21, 2009
7-25