Commissioning
GARD 8000 Distance Relay
RFL Electronics Inc.
Zone 2-Phase A to Neutral- 120% of the Line
Pre-Fault Settings
Fault Settings
Source Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
VA
69.00V
0.00
°
60.00 12.0V 0.00
°
60.0
VB
69.00V
240.00
°
60.00 69.28V 240.00
°
60.0
VC
69.00V
120.00
°
60.00 69.28V 120.00
°
60.0
IA
0.00A
0.00
°
60.00 10.00A -70.00
°
60.0
IB
0.00A
0.00
°
60.00 0.00A 0.00
°
60.0
IC
0.00A
0.00
°
60.00 0.00A 0.00
°
60.0
Expected Results:
Zone 1 restrains, Zone 2 picks up for Phase A to Neutral Fault.
Zone 3-Phase A to Neutral
Pre-Fault Settings
Fault Settings
Source Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
VA
69.00V
0.00
°
60.00 30.0V 0.00
°
60.0
VB
69.00V
240.00
°
60.00 69.28V 240.00
°
60.0
VC
69.00V
120.00
°
60.00 69.28V 120.00
°
60.0
IA
0.00A
0.00
°
60.00 10.00A -70.00
°
60.0
IB
0.00A
0.00
°
60.00 0.00A 0.00
°
60.0
IC
0.00A
0.00
°
60.00 0.00A 0.00
°
60.0
Expected Results:
Zone 1, Zone 2, Zone 4 restrain, Zone 3 picks up for Phase A to Neutral Fault.
Zone 4-Phase A to Neutral
Pre-Fault Settings
Fault Settings
Source Amplitude
Phase
Angle
Frequency
(Hz)
Amplitude
Phase
Angle
Frequency
(Hz)
VA
69.00V
0.00
°
60.00 40.0V 0.00
°
60.0
VB
69.00V
240.00
°
60.00 69.28V 240.00
°
60.0
VC
69.00V
120.00
°
60.00 69.28V 120.00
°
60.0
IA
0.00A
0.00
°
60.00 10.00A -70.00
°
60.0
IB
0.00A
0.00
°
60.00 0.00A 0.00
°
60.0
IC
0.00A
0.00
°
60.00 0.00A 0.00
°
60.0
Expected Results:
Zone 1, Zone 2, Zone 3 restrain, Zone 4 picks up for Phase A to Neutral Fault.
March 1, 2009
12-12
973.334.3100