Description of Operation
GARD 8000 Distance Relay
RFL Electronics Inc.
V_line
V_bus
Synch
Dead Line/Dead Bus
Dead Line/Live Bus
Live Line/Dead Bus
Live Line/Live Bus
Synch Check
Voltage difference
Phase difference
Frequency difference
Enable
‘1’
Enable
‘1’
Enable
‘1’
T
2 cycl
Figure 9-63. Synchro and Energizing Check Logic
9.21
POLE DISCORDANCE
The pole discordance logic will detect an abnormality of the position of the three breaker poles. If this
condition is maintained during the time setting, a three pole trip is generated. Given that the single-pole
reclose cycles will produce a pole discordance condition, the time setting should be longer than the
single pole reclose time.
Pole discordance is enabled under the “Power Swing Block and other advanced settings.”
T
0
Trip pole
discordance
52b_A
52b_B
52b_C
Figure 9-64. Pole Discordance Logic