4.2 Setting the heating/cooling
operating mode
Heating curve heating cycle mode
The heating curve can be adjusted in three points,
according to the structure and location-related con-
ditions of the building:
Base point:
The base point corresponds to the minimum set
temperature of the heating water at an outside
temperature of 20 °C. If the heating is too cold at
relatively high outside temperatures (trans-sea-
sonal period), the base point should be set higher.
Standard inlet temperature:
The standard inlet temperature corresponds to the
set temperature of the heating water at the
standard outside temperature in the building loca-
tion. If the heating is not warm enough at low out-
side temperatures, the standard inlet temperature
should be increased.
Standard outside temperature:
The standard outside temperature is dependent on
the regional location of the building and must be
set according to the region.
2
1
4
3
Fig. 6: Heating curve adjustment
1: Temperature of the heating water in °C
2: Inlet temperature heating curve
3: Return flow heating curve
4: Outside temperature in °C
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
23