background image

Setting the impulse rate of the solar medium flow rate probe

The impulse rate must only be changed if the impulse rate in the customer-provided system must be

adapted.

Menu item

Parameter

Factory setting

Impulse rate for medium flow rate

(if activated)

0 - 10 ml/Imp

5.7 ml/Imp

Manual medium flow rate

If no medium flow rate probe is installed in the solar station, a manual medium flow rate can be selected. The

heat meter can also be deactivated, if desired.

The medium flow rate is specified in order to calculate the amount of solar heat.

The value can be viewed on the flow meter when the solar pump is running.

Then set the value.

Recommendation:

adjust the medium flow rate to suit the hydraulic system provided by the customer

Set temperature of the storage tank during solar charging

Once the solar set temperature is reached, the solar cycle pump is switched off. With the collector cooling

function activated, the temperature of the storage tank can continue to rise as far as the set maximum tem-

perature.

The solar set temperature should be reduced if the hot water temperature is regularly too high or if there is

no thermostatic mixing valve installed. At the same time, when the collector cooling function is activated, the

max. temperature of the storage tank must be reduced.

Menu item

Parameter

Factory setting

Solar set temperature

5 °C - 95 °C

85 °C

REMKO recommends installing a domestic hot water mixer with solar hot water preparation.

 WARNING!

Implement measures on site to ensure sufficient scalding protection!

 

 

 

 

 

93

Summary of Contents for Smart-Control Touch

Page 1: ...manual Read the instructions prior to performing any task REMKO Smart Control Touch For the heat pump series 0203 2019 09 Edition 3 en_GB Specialist and user manual HTS WKF WKF compact WKF NEO LWM an...

Page 2: ...these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject to modificati...

Page 3: ...y 5 1 11 Transport and packaging 6 1 12 Environmental protection and recycling 6 2 Technical data 7 3 Operation General notes 8 4 Operation User level 10 4 1 Menu structure 10 4 2 Setting the heating...

Page 4: ...tal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This combina...

Page 5: ...d or mounted on stable structures walls or floors n Mobile units must be set up securely on suit able surfaces and in an upright position Sta tionary units must be permanently installed for operation...

Page 6: ...l protection and recycling Disposal of packaging All products are packed for transport in environ mentally friendly materials Make a valuable contri bution to reducing waste and sustaining raw mate ri...

Page 7: ...mW 100 Max cable length m 15 Recommended cable mm2 2 x 0 5 Dimensions Height mm 150 Width mm 80 Depth mm 35 Environment Ambient temperature C 0 70 Air humidity rH 0 95 relative non condensing Remote c...

Page 8: ...ible through the installation of further supplemen tary software available as an accessory When in an idle state the display is inactive The basic display only starts once the display is touched and i...

Page 9: ...set temperature The desired temperature for the hot water preparation of the drinking water storage tank can be adjusted here n Weather information Fig 3 Menu items in the Overview level Navigation i...

Page 10: ...4th mixed cycle 4th mixed cycle Nur WKF Duo Information Einstellungen Grund informationen Solar Warmwasser Grund einstellungen Solar Warmwasser Meldungen Fehlermeldungen Warnhinweise Schornstein fege...

Page 11: ...nts the REMKO heat pump user Relevant points that affect the safety of the complete system are only to be changed by a specialist These are only enabled in the expert level following entry of the pass...

Page 12: ...Away mode Anti freeze protection Smart Count Smart Web Smart Com Activation code Serial number Date Time Time Date Time zone Version number Hardware Software Control Panel Software Software I O 2 Lin...

Page 13: ...Hot water storage tank target temperature Hot water storage tank actual temperature S08 Hot water energy Hygiene function Circulation request S05 Circulation set temperature Circulation actual tempera...

Page 14: ...e Room actual temperature Room humidity Dew point Mixed outside temperature 3rd mixed cycle Operating mode Set temperature Actual temperature Room set temperature Room actual temperature Room humidity...

Page 15: ...alve A14 Pump speed rel A43 Pump speed rel A43 2 Pump speed rel HP 1 Pump speed rel HP 2 PV current usage Heat pump HP 1 Heat pump status Remaining idle time Defrost status Compressor status Compresso...

Page 16: ...e outdoor Fault code indoor Target temperature Enable signal Disable compressor Heat pump status Fan status Disable signal S16 energy supplier cut off Air temperature outdoor module Auxiliary heat gen...

Page 17: ...ronment Environmental energy Household Current household output Household energy Photovoltaic Photovoltaic output Photovoltaic yield Feed in power Feed in Private consumption power Private consumption...

Page 18: ...m Basic settings Language Time Date Time Date format Time format Language Time zone Display Display brightness Display off Default screen Solar Storage tank Solar set temperature Hot water Domestic ho...

Page 19: ...aptation Standard outside temp Heating Standard outside temp Cooling Inertia of the heating curve Unmixed cycle Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mod...

Page 20: ...B Time program C Time program function Room temperature reduction Room temperature increase Room unit Room temperature influence 2nd mixed cycle Operating mode Heating cycle mode Fixed value Heating...

Page 21: ...nction Room temperature reduction Room temperature increase Room unit Room temperature influence 4th mixed cycle Operating mode Heating cycle mode Fixed value Heating curve adjustment Cooling cycle mo...

Page 22: ...ht up in red or yellow in the basic display it is necessary to check which fault warning or note is displayed on the message level In order to call up the message level it is only necessary to touch t...

Page 23: ...at the standard outside temperature in the building loca tion If the heating is not warm enough at low out side temperatures the standard inlet temperature should be increased Standard outside tempera...

Page 24: ...curve settings Change the value with under the heating curve schematic and select the next value with Next Then confirm with OK Fig 7 Setting the base point 2 Standard inlet temperature The standard...

Page 25: ...ting curve parameters the heating load calculation and or energy consumption must be taken into account Differences between the installed parameters and the design of the actual building can cause the...

Page 26: ...high outside temperatures trans seasonal period the base point should be set higher Standard inlet temperature The inlet temperature corresponds to the set tem perature of the cooling water at the sta...

Page 27: ...andard inlet temperature Change the value of the setting of the inlet temper ature and the outside temperature with and select the next value with Next Then confirm with OK Fig 13 Setting the inlet te...

Page 28: ...ting e g if the underfloor system is to be cooled REMKO recom mends protecting the system with dew point moni tors in the case of panel heating Fixed value control cooling cycle mode Specify the set t...

Page 29: ...g 16 Example hydraulic diagram A Combination buffer tank B Room temperature humidity probe 1 Heat pump inlet line 2 Heat pump return flow 3 Hot water 4 Cold water 5 Unmixed cycle 6 Mixed cycle CAUTION...

Page 30: ...t is undershot at the external probe The basic setting of the REMKO Smart Control Touch controller is 16 degrees if no adjustment has been made to the desired room set temperature The adjustment of th...

Page 31: ...alue 0 0 C gives a desired room tempera ture of 20 C You can change this value to 10 C room target temperature 30 C or optionally to 10 C room target temperature 10 C In order to specify the point of...

Page 32: ...Now proceed as follows in the parameter level heating cooling Fig 20 Start screen Fig 21 Select Settings menu item REMKO Smart Control Touch 32...

Page 33: ...reached at the external probe Please note the diagram in Fig 17 for infor mation on which value should be set here An example setting The colder hotter parameter room target temper ature of 2 C means...

Page 34: ...andard the longer the possible setting of the building time con stant This value can only be changed in the expert level and must generally only be saved once You will find the parameter Building time...

Page 35: ...the WPA 2 encryption security standard Installation in house The central controller for the REMKO heat pump via a smart phone or other mobile devices can be installed virtually anywhere in the buildi...

Page 36: ...so touch the REMKO logo in the upper right corner of the display Fig 26 Access to the expert level After activating the expert level by touching the corresponding REMKO logo a password is required To...

Page 37: ...the expert level is 0321 If this password has not already been changed the expert level is enabled after entering this password Fig 28 Password input Select the Settings level here by touching it Fig...

Page 38: ...level select the Basic settings parameter Fig 30 Select Basic settings menu item The Interfaces parameter appears in the Basic settings level Touch to select this Fig 31 Select Interfaces menu item R...

Page 39: ...twork menu item In the Network level you can now connect the heat pump with your router To do so first select the Authentication parameter 2 1 4 3 Fig 33 Authentication of the WLAN network 1 Authentic...

Page 40: ...push button function Now scroll down to select the SSID parameter As described in the following enter and save the name of your WLAN network and the corre sponding password To enter the SSID select t...

Page 41: ...ck this via the Net work USB parameter Connect must be dis played here if all data is correct To view the heat pump data on a smartphone tablet or laptop make a note of the IP address that comes after...

Page 42: ...controller If you require the option of accessing the parame ters of your controller outside of the actual WLAN network this is only possible with the REMKO Smart Web function This supplementary softw...

Page 43: ...ing the expert level by touching the corresponding icon a password is required To enter the password at this level use and then proceed to the next item with Next Once you have finished entering the p...

Page 44: ...parameter levels are visible Select the Settings level here by touching it Fig 42 Select Settings menu item After selecting the Settings level select the Basic settings parameter Fig 43 Select Basic...

Page 45: ...Select System configuration menu item After selecting the System configuration level select the Heat pump parameter Then deactivate the heat pump in the Heat pump level by touching activated and chang...

Page 46: ...d With deactivation of the heat pump the second heat generator e g the REMKO Smart Serv auxil iary heater or a condensing unit installed in the system is active Fig 46 Activation of a 2nd heat generat...

Page 47: ...ay Fig 47 Access to the expert level The expert level is password protected After entering the password 0321 the authorised specialist accesses the expert level without confirming the code This passwo...

Page 48: ...n accordance with the requirements the REMKO heat pump user Relevant points that affect the safety of the complete system are only to be changed by a specialist These are only enabled in the expert le...

Page 49: ...Heat pump Heat pump I O2 HP2 Only WKF Duo Only WKF Duo Only WKF Duo LWM Duo Additional heat generators Additional heat generators Meter readings Energy meter Probe correc tion Program Output Manual Mo...

Page 50: ...item Level 4 menu item Basic information Status Detected unit Control algorithm Current operating mode Previous operating mode Room climate Party mode Away mode Anti freeze protection Power consumpti...

Page 51: ...sion HP 1 Revision HP 2 Network IP address Subnet Gateway MAC address Network USB USB interface IP address Subnet Gateway MAC address WLAN status Licence information Solar Pump control signal A01 Coll...

Page 52: ...rate S27 Tap volume Circulation request S05 Circulation set temperature Circulation actual temperature S05 Circulation pump A04 Stored energy Stored energy Buffer tank temperature S09 Hot water tempe...

Page 53: ...humidity Dew point Mixed outside temperature Pump speed rel A41 Heating cycle mixer position A20 A21 KNX status KNX setpoint adjustment 2nd mixed cycle Operating mode Set temperature Actual temperatu...

Page 54: ...atus KNX setpoint adjustment 4th mixed cycle Operating mode Set temperature Actual temperature Inlet temperature S06 2 Return temperature S14 2 Room set temperature Room actual temperature Room humidi...

Page 55: ...n temperature S15 HP 1 Return temperature HP 2 Return temperature mixed Set medium flow rate Actual medium flow rate S24 HP 1 Actual medium flow rate S24 2 Actual medium flow rate HP 2 Pump speed rel...

Page 56: ...off Compressor frequency Max inlet temperature Fan speed rpm Fan speed Air temperature outdoor unit Water inlet temperature Water outlet temperature Suction gas temperature Matrix temperature Heat gas...

Page 57: ...atus Fault status Enable signal Disable compressor Heat pump status Disable signal S16 energy supplier cut off Compressor frequency Max inlet temperature Fan speed Fan speed Air temperature outdoor un...

Page 58: ...Level 2 menu item Level 3 menu item Heat pump I O 2 HP 2 continued Overheating Compressor starts Run time minutes Run time hours Envelope status Inverter status Anti freeze protection status Only LWM...

Page 59: ...r yield day Solar yield week Solar yield month Solar yield year Solar yield Heat pump Thermal power heat pump Thermal energy day Thermal energy week Thermal energy month Thermal energy year Thermal en...

Page 60: ...c Photovoltaic output PV yield day PV yield week PV yield month PV yield year Photovoltaic yield Feed in power Feed in day Feed in week Feed in month Feed in year Feed in Private consumption power Pri...

Page 61: ...actual temperature S08 Buffer tank temperature S09 Outside temperature S10 KNX outside temperature Return temperature S11 Return temperature S11 2 Inlet temperature S12 Inlet temperature S12 2 Inlet t...

Page 62: ...Impulse counter status S25 Impulse counter status S26 Medium flow rate S 27 Impulse counter S 28 Impulse counter S 29 KNXnet IP IP for the KNX interface MAC for the KNX interface IA for the KNX interf...

Page 63: ...er sion Level 2 menu item Level 3 menu item Level 4 menu item Level 5 menu item Basic settings Language Time Date Time Date format Time format Language Temperature unit Decimal separator Volume unit P...

Page 64: ...witching Heating cooling status SMT operating mode switching SMT operating mode status Outside temperature Room set temperature Dewing non functional Hot water target tempera ture Hot water actual tem...

Page 65: ...me Date Unmix HC room target temp 1st mixed HC room target temp 2nd mixed HC room target temp 3rd mixed HC room target temp 4th mixed HC room target temp Unmix HC presence object 1st mixed HC presence...

Page 66: ...nerator PV current usage Graduated tariffs Domestic hot water heating Hot water circulation Hygiene function Unmixed cycle 1st mixed cycle 2nd mixed cycle 3rd mixed cycle 4th mixed cycle System separa...

Page 67: ...perature Solar set temperature hysteresis Collector cooling function ON temp Storage tank max temp Pump setting Pump type Solar speed control system Asynchronous speed control system Min pump speed A0...

Page 68: ...tion Speed in hot water A43 Pump parallel operation Switch off delay Hot water valve Circulation Circulation type Circulation set temperature Target temperature hysteresis Time program Running time Di...

Page 69: ...nation Value range Factory setting Customer system Set temperature 60 C 75 C 60 C Day of activation Mon Sun Monday Time of activation Hrs Mins 20 00 Inspection time 24 h 72 h 72 h Storage tank volume...

Page 70: ...ion we recom mend ending this function manually by deactivating it Floor screed function status Start end temperature Max temperature Heating phase increment Drying time Time at high temperature Incre...

Page 71: ...ting cycle mode Fixed value Heating curve adjustment Cooling cycle mode Fixed value Cooling curve adjustment Time program A Time program B Time program C Time program function Room temperature reducti...

Page 72: ...tment Time program A Time program B Time program C Time program function Room temperature reduction Room temperature increase Room unit Room temperature influence Dew point monitoring Dew point distan...

Page 73: ...g curve adjustment Time program A Time program B Time program C Time program function Room temperature reduction Room temperature increase Room unit Room temperature influence Dew point monitoring Dew...

Page 74: ...Time program function Room temperature reduction Room temperature increase Room unit Room temperature influence Dew point monitoring Dew point distance Max inlet temperature Delta T regulation Delta...

Page 75: ...ime program C Time program function Room temperature reduction Room temperature increase Room unit Room temperature influence Dew point monitoring Dew point distance Max inlet temperature Delta T regu...

Page 76: ...ump speed A43 Cooling pump actuation Manual defrosting HP 1 Manual defrosting HP 2 Reset malfunction Bivalence point Bivalence point heating Bivalence point hot water Output restriction Time program O...

Page 77: ...hot water influence Short term heating influence Continuous heating influence PV current usage PV personal use variant Power tariff 1 Feed in tariff Personal use tariff Factor for PV power surplus Da...

Page 78: ...er Heat pump electrical Meter constant S25 Household meter Meter constant S26 Reference meter Meter constant S26 Feed meter Meter constant S29 Photovoltaics yield Meter constant S28 Probe correction O...

Page 79: ...On Off Changeover valve cooling A14 Auto On Off Mixing valve 1st mixed heating cycle A20 A21 Open Stop Close Auto Mixing valve 3rd mixed heating cycle A20 2 21 2 Open Stop Close Auto Bypass valve A22...

Page 80: ...250 C Storage tank temperature lower S02 Probe value stipulated value Temperature S02 60 C 250 C Solar inlet temperature S03 Probe value stipulated value Temperature S03 60 C 250 C Solar return tempe...

Page 81: ...S11 2 Probe value stipulated value Temperature S11 2 60 C 250 C 1st mixed heating cycle inlet temperature S12 Probe value stipulated value Temperature S12 60 C 250 C 3rd mixed heating cycle inlet temp...

Page 82: ...t pump fault S20 On Off Auto Compressor active S21 On Off Auto Defrosting thawing active S22 On Off Auto Medium flow rate solar S23 Probe value stipulated value Medium flow rate S23 0 l min 100 l min...

Page 83: ...enu item Mode Normal operation test mode Hot water valve Deactivated activated Running time 15 90 minutes Messages menu item Expert This menu displays warnings warning information and error messages I...

Page 84: ...The parameters of the installation level must be enabled on the heat pump and a number of these must be adjusted to the site configuration Setting the country Please confirm this parameter in order to...

Page 85: ...avings time to occur automatically The respective time zone in winter must be specified Central Europe GER FR IT ES PL CET Central European Time Berlin Paris If UTC Universal Time Coordinated is selec...

Page 86: ...vious counter readings Menu item Parameter Factory setting Restore counter readings YES NO NO Load user settings When first installing the controller this parameter is confirmed with NO If a new softw...

Page 87: ...ters are then queried Pay attention to information on the display Menu item Parameter Factory setting Domestic hot water heating Activated Deactivated Deactivated Storage tank set temperature Desired...

Page 88: ...tion Circulation set temperature temperature guided circulation Desired set temperature for temperature guided circulation This should be set at least 5 C below the set temperature for the hot water s...

Page 89: ...activated Deactivated Activated Operating mode Select the operating mode for the unmixed circuit Setting heating cycle mode This is where you can select between the different heating cycle modes The c...

Page 90: ...o retain heat The building time constant is dependent upon the type of building see table The value is also dependent on individual temperature per ception and so the information in the table should o...

Page 91: ...activated again at a later date Activation if a solar plant is available Menu item Parameter Factory setting Solar plant Deactivated Deactivated Activated Selecting the pump system Select the pump sy...

Page 92: ...u item Parameter Factory setting Solar speed control system Deactivated Deactivated Activated Asynchronous speed control system Menu item Parameter Factory setting Asynchronous speed control system On...

Page 93: ...um flow rate to suit the hydraulic system provided by the customer Set temperature of the storage tank during solar charging Once the solar set temperature is reached the solar cycle pump is switched...

Page 94: ...er 55 GLYTHERMIN P44 Acquisition of the stored energy via the S 09 probe If heating is to be provided from the available solar yield if required this parameter must be activated If another heat genera...

Page 95: ...and the installed storage tank size Activation of the hygiene function is only possible in the expert level Accessing the expert level is described in chapter Structure of the expert level on page 47...

Page 96: ...on pump is installed on the I O module terminal A04 of the heat pump this is activated via the circulation pump function 2nd heat generator If the second heat generator in this level is deactivated it...

Page 97: ...fter activation the cycle is now enabled and can be set in the User level and in the Expert level of the connected heating cycle configuration For this purpose implement the changes with the grey slid...

Page 98: ...nstaller We recommend adapting plant specific parameters such a heating limits and bivalence point to the design data You can find further hydraulics examples at www remko de Hydraulic circuit diagram...

Page 99: ...ulation running time 1 min 15 mins 5 min Disable switch on 1 min 15 mins 5 min Unmixed heating cycle Activated Deactivated Activated Operating mode Heating cooling Heating and cooling Heating Heating...

Page 100: ...andard outside temperature Deactivated System separation FBH Activated Deactivated Deactivated Setpoint increase 0 10 K Deactivated Building time constant 0 h 100 h 10 h Standard heating load 0 kW 25...

Page 101: ...gnal ID6010 Heat pump compressor start I O 2 Heat pump compressor start ID6012 Defrosting HP I O 2 Defrost heat pump ID6020 Pump internal after run time The internal pump runs at a reduced speed durin...

Page 102: ...alarm HP 1 The compressor ran outside its usable limits for too long ID7057 High heat gas tempera ture HP 1 The maximum hot gas temperature has been exceeded ID7058 4 way valve fault HP 1 Pressure dif...

Page 103: ...obe T3 was not detected ID7088 Fault with probe T4 HP 2 Temperature probe T4 was not detected ID7089 Fault with probe T5 HP 2 Temperature probe T5 was not detected ID7090 Fault with probe T7 HP 2 Temp...

Page 104: ...ircuit external probe ID7208 Open contact refrigerant probe S07 Open contact refrigerant probe ID7209 Short circuit refrig erant probe S07 Short circuit refrigerant probe ID7210 Open contact circula t...

Page 105: ...contact mixed heating cycle return temperature probe ID7239 Short circuit mix heating cycle return temp probe S11 Short circuit mixed heating cycle return temperature probe ID7240 Connection to the K...

Page 106: ...nd its connection ID7264 Inlet temperature probe error PC Inlet temperature probe error please check the inlet tempera ture probe on the inverter board and its connection ID7267 Outlet temperature pro...

Page 107: ...error between com kit and outdoor unit communication could not be established or incorrect board version ID7292 WKF fault code E231 Short circuit or open contact evaporator temperature probe motherboa...

Page 108: ...segment dis play and inverter board ID7311 WKF fault code E466 Under voltage or over voltage in the intermediate DC circuit of the inverter ID7312 WKF fault code E469 Voltage probe fault in the interm...

Page 109: ...occurred over night ID8104 Medium flow rate too low HP 2 The medium flow rate is too low to start the heat pump ID8105 Set medium flow rate HP1 The flow rate has dropped below the set medium flow rate...

Page 110: ...uration for the defrost has been exceeded ID8223 SD card error host SD card error host The SD card is either not inserted correctly or an error has occurred ID8224 SD card error SD card error CP The S...

Page 111: ...mode 87 89 Pump system 91 Restore counter readings 86 Set temperature of the storage tank during solar charging 93 Setpoint increase 90 Solar heat meter 92 Solar plant 91 Solar speed control system 92...

Page 112: ...e probe 92 Operating mode 87 89 Pump system 91 Restore counter readings 86 Set temperature of the storage tank during solar charging 93 Setpoint increase 90 Solar heat meter 92 Solar plant 91 Solar sp...

Page 113: ...113...

Page 114: ...REMKO Smart Control Touch 114...

Page 115: ......

Page 116: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Reviews: