Overview of all of the parameters relevant for the static or dynamic hygiene function.
Static
Dynamic
Description
Set temperature
Setting the target temperature
Day of activation
-
Setting the first weekday
Time of activation
-
Setting the starting time
-
Inspection time
The hygiene function is only active if the tank contents
of the hot water storage tank have not been changed
for 72 hours. The test time can be shortened here if the
customer wishes
-
Storage tank volume
Setting of the hot water storage tank between 0 and
1000 l. Factory setting: 300 litres
-
Pulse valency
Setting dependent on the flow sensor installed (DN15/
DN25, see "Flow sensor" operating instructions)
Max. duration until cancellation
After the set time has elapsed, the hygiene function is
interrupted if it has not already been switched off via
normal operation
Circulation pump
If a circulation pump has been installed in the factory
system, this must be operational when the hygiene
function is activated. If the circulation pump is installed
on the I/O module (terminal A04) of the heat pump, this
is activated via the circulation pump function
2nd heat generator
If the second heat generator in this level is deactivated,
it is enabled in accordance with the set bivalency point
after the hygiene function has been enabled. If value for
hot water does not fall below the set bivalency point,
the second heat generator is enable as required. If
value for hot water does fall below the set bivalency
point, it is enabled immediately after the hygiene func-
tion is called up. The definitive bivalency point for your
system can be found in the Smart-Control Touch con-
troller instructions in the expert level under "Settings/
Heat pump".
If the second heat generator is activated in this level,
the second heat generator is immediately enabled with
activation of the hygiene function.
With bivalent systems (wall heating device/ oil/gas
boiler), the hygiene function is exclusively activated via
the second heat generator.
After the parameters described above, activation of the hygiene function is completed. To return to the basic
display, exit the parameter levels via the arrow at the bottom left.
REMKO Smart-Control Touch
96