Temperature setpoints
Pressing the
key next to
"TEMPERATURE
SET POINTS"
in the "TIMER" menu accesses the
submenu for configuring the setpoints for "AUTO-
MATIC OPERATION". The temperature selection
submenu includes the following items:
n
Comfort (Cm)
n
Reduction (Ec)
n
Anti-freeze protection (An)
n
Neutral zone (Xd)
To change the setpoints, press the key corre-
sponding to the desired point
to access the
regulation screen, then adjust the value with the
"up" and "down" arrow keys (setting range -10.0°C,
+90.0°C). Press "OK" to confirm the desired set-
point. The temperatures are set in 0.1° steps.
The setpoints set for "MANUAL OPERATION"
are independent of the values set in this menu.
The
"Neutral zone (Xd)"
represents the hysteresis
interval for controlling ON/OFF operation (range
0.0°C; +50.0°C). The Xd value is set to 1.0°C by
default.
To control the room temperature, set this value
to 0.2°C.
10:15
Calendario
Prog. Timer
Timer
Temperatursollwerte
10:15
Absenkung (Ec) °C
Frostschutz (An) °C
Neutrale Zone (Xd) °C
Komfort (Cm) °C
Temperatursollwerte
20.0
12.0
2.0
1.0
OK
Komfort (Cm)
20.0
°C
10:15
Komfort (Cm)
OK
Mon 01 Jan
Mon 01 Jan
Mon 01 Jan
Calendar
Temperature setpoints
Temperature setpoints
Temperature setpoints
Comfort (Cm)
Neutral zone (Xd)
Anti-freeze protection
(An)
Reduction (Ec)
Comfort (Cm)
Comfort (Cm)
Fig. 20: Set temperature setpoints
23