Solid-State Power Controller

User’s Manual

DIN-A-MITE Solid-State Power Controller

Please  consult this user’s manual when you
place your new DIN-A-MITE into service. It
contains all the necessary information to mount
and wire the product into the application. This
manual also contains all user-pertinent
specifications and semiconductor fusing
recommendations. Refer to national and local
electrical code safety guidelines whenever you
install electrical  equipment.

This DIN-A-MITE product is capable of
 switching up to 40 amps single-phase; 33 amps
3-phase, 2-leg; and 22 amps 3-phase, 3-leg at
600V

Å

(ac). (See the output  rating curve in the

specifications section of this  manual.) The DIN-

A-MITE is electrically touch-safe, and includes
DIN rail or standard back panel mounting. An
optional shorted SCR (silicon controlled rectifier)
alarm feature is available on specific  models.
UL

®

508-listed, C-UL

®

and CE with filter.

The DIN-A-MITE solid-state power controller is
designed and manufactured by Watlow in
Winona, Minnesota.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DB10-02C0-0000

Page 1: ...nstall electrical equipment This DIN A MITE product is capable of switching up to 40 amps single phase 33 amps 3 phase 2 leg and 22 amps 3 phase 3 leg at 600V ac See the output rating curve in the spe...

Page 2: ...00 of span 4 3 to 19 7mA Temperature stability is less than 0 15 C change Alarm not available on multizone models Shorted SCR Alarm Option Alarm state when the input command signal off and a 10 A or m...

Page 3: ...Table Model Current at 50 C 122 F DB10 35A DB20 DB80 25A DB30 DB90 17A Note Recommended fusing options to meet 200KA SCCR type 1 and 2 approved All other fuse and SCR combinations are defaulted to 5K...

Page 4: ...ins vertically 1 1 2 Mount Dismount Front Allowance for 8 fastener metric M4 Grounding screw 6 Allowance for 8 fastener metric M4 DIN EN 50022 35 mm by 7 5 mm rail clipping distance 34 7 mm 1 366 in t...

Page 5: ...13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac Input 7 8 9 10 11 12 13 Zone 1 V dc Input Zone 2 V dc Input Zone 3 V dc Input 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac...

Page 6: ...al injury or death NOTE Use a grounding conductor terminal plate fork terminal having upturned lugs or the equivalent to hold the wire in position Maximum 6 mm2 10 AWG wire Torque Guidelines Properly...

Page 7: ...ountry specific standard wiring practices to install and operate the DIN A MITE Failure to do so may result in damage to equipment and property and or injury or loss of life NOTE If you plan to wire m...

Page 8: ...r each DIN A MITE used Torque Guidelines Properly torque line and load terminals to 1 4 Nm 12 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 mon...

Page 9: ...the alternative latching circuit section below V 13 14 Triac RY1 Coil Reset Switch RY1A L1 L2 RY1B Normally open Common Normally closed External alarm relay contacts set A External alarm relay contac...

Page 10: ...connection NOTES 1 Use of an external filter is required to comply with conducted emissions limits See note 4 below 2 A Line Impedance Stabilization Network LISN was used for conducted emissions measu...

Page 11: ...G All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to properly suppress EMI however...

Page 12: ...n shipment Your P O number Detailed description of the problem Any special instructions Name and phone number of person returning the product 2 Prior approval and an RMA number from the Customer Servi...

Reviews: