WATLOW DIN-A-MITE Style B User's Manual

1. Push the unit in and down to catch the rail

hook on top of the rail.

2. Rotate the bottom of the unit in toward the

rail.

3. The rail clasp will audibly “snap” into place.

If the DIN-A-MITE does not snap into place,
check to see if the rail is bent.

4. Mount the cooling fins vertically.

ç

3

WARNING:
Only authorized and
qualified personnel should
be allowed to install and
perform preventive and
corrective maintenance on
this unit. Failure to follow
this guideline could result
in damage to equipment,
and personal injury or
death.

5

WARNING:
Hot surface, do not touch
the heat sink. Failure to
follow this guideline could
result in personal injury.

ç

Mount the cooling fins
vertically.

1

1

2

Mount

Dismount

Front

Allowance for #8 fastener, 
metric = M4

Grounding screw (#6)

Allowance for #8 fastener, 

metric = M4

DIN-EN 50022 35 mm by 7.5 mm rail
(clipping distance 34.7 mm (1.366 in)

to 35.3 (1.390 in)

49 mm

(1.91 in)

49 mm

(1.92 in)

83 mm

(3.25 in)

54 mm

(2.11 in)

46 mm

(1.81 in)

38 mm

(1.51 in)

Unit Dimensions - Rail-Mounted

1. Press down on the release tab while rotating

the unit up and away from the rail.

4

3

Top

8

3 mm

(3.25 in)

124 mm
(4.

88

 in)

13 mm

(0.50 in)

Side 

b

y side

 clearance 

for 

w

ire ro

u

ting

Side

102 mm (4.00 in) clearance for air flo

w

and 

w

ire 

b

ending radi

u

s

Zero electrical clearance re

qu

ired

102 mm (4.00 in) clearance for air flo

w

 

and 

w

ire 

b

ending radi

u

s

Rail release ta

b

 

(p

u

ll do

w

n)

94 mm

(3.69 in) 75 mm

(2.97 in)

26 mm

(1.03 in)

102 mm
(4.00 in)

40 mm

(1.56 in)

71 mm

(2.

8

0 in)

102 mm
(4.00 in)

41 mm

(1.60 in)

ç
Ó

3

5

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DB10-02C0-0000

Page 1: ...nstall electrical equipment This DIN A MITE product is capable of switching up to 40 amps single phase 33 amps 3 phase 2 leg and 22 amps 3 phase 3 leg at 600V ac See the output rating curve in the spe...

Page 2: ...00 of span 4 3 to 19 7mA Temperature stability is less than 0 15 C change Alarm not available on multizone models Shorted SCR Alarm Option Alarm state when the input command signal off and a 10 A or m...

Page 3: ...Table Model Current at 50 C 122 F DB10 35A DB20 DB80 25A DB30 DB90 17A Note Recommended fusing options to meet 200KA SCCR type 1 and 2 approved All other fuse and SCR combinations are defaulted to 5K...

Page 4: ...ins vertically 1 1 2 Mount Dismount Front Allowance for 8 fastener metric M4 Grounding screw 6 Allowance for 8 fastener metric M4 DIN EN 50022 35 mm by 7 5 mm rail clipping distance 34 7 mm 1 366 in t...

Page 5: ...13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac Input 7 8 9 10 11 12 13 Zone 1 V dc Input Zone 2 V dc Input Zone 3 V dc Input 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac...

Page 6: ...al injury or death NOTE Use a grounding conductor terminal plate fork terminal having upturned lugs or the equivalent to hold the wire in position Maximum 6 mm2 10 AWG wire Torque Guidelines Properly...

Page 7: ...ountry specific standard wiring practices to install and operate the DIN A MITE Failure to do so may result in damage to equipment and property and or injury or loss of life NOTE If you plan to wire m...

Page 8: ...r each DIN A MITE used Torque Guidelines Properly torque line and load terminals to 1 4 Nm 12 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 mon...

Page 9: ...the alternative latching circuit section below V 13 14 Triac RY1 Coil Reset Switch RY1A L1 L2 RY1B Normally open Common Normally closed External alarm relay contacts set A External alarm relay contac...

Page 10: ...connection NOTES 1 Use of an external filter is required to comply with conducted emissions limits See note 4 below 2 A Line Impedance Stabilization Network LISN was used for conducted emissions measu...

Page 11: ...G All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to properly suppress EMI however...

Page 12: ...n shipment Your P O number Detailed description of the problem Any special instructions Name and phone number of person returning the product 2 Prior approval and an RMA number from the Customer Servi...

Reviews: