WATLOW DIN-A-MITE Style B User's Manual

7

 

Alarm Relay 

or Indicator

V~

120 or 240 V~

@ 300 mA maximum 

energizes on alarm

1A

Current

Transformer 

(CT)

Heater

Load Wire

7
8
9

10
11
12
13
14
15
16

1 2 3

4 5 6

CT

Alarm

Current Transformer and Alarm Wiring

ç

Ó

1

Ó

2

Ó

3

DB _ _ - _ _ _ _ - S_ _ _ 

The Watlow DIN-A-MITE alarm
option provides a common alarm
output for shorted SCR conditions.

This is a non-latching alarm.

A shorted SCR alarm is detected
when there is no command signal
and a load current is detected. The
alarm output is then energized.

Load Current 

Passes of Load 

Wire Through the 

Current Transformer

5 to 9A

2

10 to 30A

1

T1

T2

T3

Heater

Current

Transformer (CT)

7
8
9

10
11
12
13
14
15
16

1 2 3

4 5 6

CT

Neutral

3-phase, 3-leg Current Transformer Wiring

T1

T2

T3

Heater

Current

Transformer (CT)

7
8
9

10
11
12
13
14
15
16

1 2 3

4 5 6

CT

3-phase, 2-leg Current Transformer Wiring

ç

Ó

1

Ó

2

Ó

3

ç

Ó

1

Ó

2

Ó

3

ç

Ó

1

WARNING:
Use National Electric (NEC)
or other country-specific
standard wiring practices
to install and operate the
DIN-A-MITE. Failure to do
so may result in damage to
equipment and property,
and/or injury or loss of life.

NOTE: If you plan to wire
 multiple DIN-A-MITE alarm
outputs, you need to
include an intermediate
relay for each DIN-A-MITE
used.

Ó

2

WARNING:
Wiring examples show L2
in phase-to-phase, 200 V

Å

(ac) and above
configuration. In phase-to-
neutral, 100V

Å

(ac) and

above  applications, L2 is
neutral and must not be
fused or switched. Failure
to follow this guideline
could result in personal
injury or death.

Ó

3

WARNING:
Only authorized and
qualified personnel should
be allowed to install and
perform preventive and
corrective maintenance on
this unit. Failure to follow
this guideline could result
in damage to equipment,
and personal injury or
death.

Torque Guidelines

• Properly torque line and 

load terminals to 1.4 Nm 
(12 in-lb).

• Retorque after 48 hours 

to minimize wire cold 
flow.

• Retorque line and load 

terminals every 3 to 6 
months.

This configuration is
for a 4 wire configured
heater only!

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DB10-02C0-0000

Page 1: ...nstall electrical equipment This DIN A MITE product is capable of switching up to 40 amps single phase 33 amps 3 phase 2 leg and 22 amps 3 phase 3 leg at 600V ac See the output rating curve in the spe...

Page 2: ...00 of span 4 3 to 19 7mA Temperature stability is less than 0 15 C change Alarm not available on multizone models Shorted SCR Alarm Option Alarm state when the input command signal off and a 10 A or m...

Page 3: ...Table Model Current at 50 C 122 F DB10 35A DB20 DB80 25A DB30 DB90 17A Note Recommended fusing options to meet 200KA SCCR type 1 and 2 approved All other fuse and SCR combinations are defaulted to 5K...

Page 4: ...ins vertically 1 1 2 Mount Dismount Front Allowance for 8 fastener metric M4 Grounding screw 6 Allowance for 8 fastener metric M4 DIN EN 50022 35 mm by 7 5 mm rail clipping distance 34 7 mm 1 366 in t...

Page 5: ...13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac Input 7 8 9 10 11 12 13 Zone 1 V dc Input Zone 2 V dc Input Zone 3 V dc Input 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac...

Page 6: ...al injury or death NOTE Use a grounding conductor terminal plate fork terminal having upturned lugs or the equivalent to hold the wire in position Maximum 6 mm2 10 AWG wire Torque Guidelines Properly...

Page 7: ...ountry specific standard wiring practices to install and operate the DIN A MITE Failure to do so may result in damage to equipment and property and or injury or loss of life NOTE If you plan to wire m...

Page 8: ...r each DIN A MITE used Torque Guidelines Properly torque line and load terminals to 1 4 Nm 12 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 mon...

Page 9: ...the alternative latching circuit section below V 13 14 Triac RY1 Coil Reset Switch RY1A L1 L2 RY1B Normally open Common Normally closed External alarm relay contacts set A External alarm relay contac...

Page 10: ...connection NOTES 1 Use of an external filter is required to comply with conducted emissions limits See note 4 below 2 A Line Impedance Stabilization Network LISN was used for conducted emissions measu...

Page 11: ...G All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to properly suppress EMI however...

Page 12: ...n shipment Your P O number Detailed description of the problem Any special instructions Name and phone number of person returning the product 2 Prior approval and an RMA number from the Customer Servi...

Reviews: