2

WATLOW DIN-A-MITE Style B User's Manual

General Specifications

Operator Interface

• Command signal input and indication light
• Alarm output and indication light
• Input indicator LED

Amperage Rating

• See the output rating curve chart on page 3.
• Ratings are into a resistive heater load.
• Maximum surge current for 16.6 milliseconds, 380 A

peak

• Maximum I

2

t for fusing is 4000 A

2

s

• Latching current: 200mA minimum 
• Holding current: 100mA minimum
• Off-state leakage 1mA at 25°C (77°F) maximum
• Power Dissipation: 1.2 watts per amp switched
• 200KA SCCR type 1 and 2 approved with the

recommended fusing (see page 3)

Line Voltage

• 24 to 48V~ (ac) units: 20.4V~ minimum to 53V~

maximum

• 120 to 240V~ (ac) units: 48V~ minimum to 265V~

maximum

• 277 to 600V~ (ac) units: 85V~ minimum to 660V~

maximum

Control Mode, Zero-Cross

• Input Control Signal Type C: V

Î

(dc) input contactor.

To increase service life, the cycle time should be less
than 3 seconds.

• Input Control Signal Type K: V~ (ac) input contactor.

To increase service life, the cycle time should be less
than 3 seconds.

• Input Control Signal Type F: 4 to 20mA

Î

(dc)

proportional variable time base control.

Input Command Signal

AC contactor

24V

Å 

±10%, 120V

Å 

+10%/-25%, 240V

Å

(ac)

+10%/-25% @ 25mA maximum per controlled leg

• Do not use the DIN-A-MITE Vac-input models with a

temperature controller that includes an RC snubber
circuit across its output. Remove the RC snubber
circuit before placing the DIN-A-MITE into service.

DC Contactor

4.5V

Î

to 32V

Î

(dc): maximum  current @ 4.5V

Î

(dc)

is 6.0mA per leg, plus 2mA per LED used.

Loop powered linear current

4mA

Î

to 20mA

Î

(dc): loop-powered. Input Type 

F0 option only. (Requires current source 
with 8.0V

Π

(dc) available. No more than two DIN-A-

MITE inputs connected in series)

Linearity (Input Control Signal Type F)

• Full on point 19.5 to 19.9mA

Î

(dc), maximum voltage

of 6.2V peak.

• ±5% input to output power accuracy, 0% to 100% of

span (4.3 to 19.7mA).

• Temperature stability is less than 0.15%/°C change.

Alarm 

(not available on multizone models)

Shorted SCR Alarm Option

• Alarm state when the input command signal off and a

10 A or more load current is detected by the current
transformer (two turns required for 5A and three turns
for 2.5A).

Alarm output  

• Energizes on alarm, non-latching
• Triac 24 to 240V~ (ac), external supply with a current

rating of 300mA @ 25°C (77°F), 200mA @ 50°C
(122°F), 100mA @ 80°C (176°F) and a holding
current of 200µA with a latching current of 5mA
typical.

Agency Approvals

• ROHS
• CE with proper filter:

2004/108/EC Electromagnetic Compatibility Directive

EN 61326: Industrial Immunity Class A emissions

2006/95/EC Low Voltage Directive

EN 50178 Safety Requirements

Installation category III, pollution degree 2

UL

®

508 listed and C-UL

®

, File E73741

Input Terminals

• Compression: Will accept 0.2 to 1.5 mm

2

(24 to 16

AWG) wire 

• Torque to 0.5 Nm (4.4 in-lb) maximum with a 3.5 mm

(1/8 in) blade screwdriver

• Wire strip length 5.5 mm (0.22 in)
• Line and load wire insulation rating must be 75C or

higher, copper conductor only

Line and Load Terminals

• Compression: Will accept 0.75 to 10 mm2 (18 to 8

AWG) wire

• Torque to 1.4 Nm (12 in-lb) with a 6.4 mm (1/4 in)

blade screwdriver, or a Type 1A #2 Pozi driver.

• Retorque after 48 hours to minimize wire cold flow.
• Retorque line and load terminals every 3 to 6 months.
• Wire strip length 6.35 mm (0.25 in)
• Ground terminal use spade terminal for No. 8 screw,

with upturned lugs.

Operating Environment

• See the output rating curve.
• 0 to 90% RH (relative humidity), non-condensing
• Storage temperature: -40 to +85°C (-40 to 185°F)
• Insulation only tested to 3,000 meters

DIN Rail Mount

• DIN EN 50022, 35 mm by 7.5 mm
• Minimum clipping distance: 34.8 mm (1.37 in)
• Maximum clipping distance: 35.3 mm (1.39 in)

Note: Mount cooling fins vertically.

Back Panel Mount

• Four mounting holes M4 (No. 8) fastener

Weight

• 0.7 kg (1.6 lb)

Specifications are subject to change without notice.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DB10-02C0-0000

Page 1: ...nstall electrical equipment This DIN A MITE product is capable of switching up to 40 amps single phase 33 amps 3 phase 2 leg and 22 amps 3 phase 3 leg at 600V ac See the output rating curve in the spe...

Page 2: ...00 of span 4 3 to 19 7mA Temperature stability is less than 0 15 C change Alarm not available on multizone models Shorted SCR Alarm Option Alarm state when the input command signal off and a 10 A or m...

Page 3: ...Table Model Current at 50 C 122 F DB10 35A DB20 DB80 25A DB30 DB90 17A Note Recommended fusing options to meet 200KA SCCR type 1 and 2 approved All other fuse and SCR combinations are defaulted to 5K...

Page 4: ...ins vertically 1 1 2 Mount Dismount Front Allowance for 8 fastener metric M4 Grounding screw 6 Allowance for 8 fastener metric M4 DIN EN 50022 35 mm by 7 5 mm rail clipping distance 34 7 mm 1 366 in t...

Page 5: ...13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac Input 7 8 9 10 11 12 13 Zone 1 V dc Input Zone 2 V dc Input Zone 3 V dc Input 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac...

Page 6: ...al injury or death NOTE Use a grounding conductor terminal plate fork terminal having upturned lugs or the equivalent to hold the wire in position Maximum 6 mm2 10 AWG wire Torque Guidelines Properly...

Page 7: ...ountry specific standard wiring practices to install and operate the DIN A MITE Failure to do so may result in damage to equipment and property and or injury or loss of life NOTE If you plan to wire m...

Page 8: ...r each DIN A MITE used Torque Guidelines Properly torque line and load terminals to 1 4 Nm 12 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 mon...

Page 9: ...the alternative latching circuit section below V 13 14 Triac RY1 Coil Reset Switch RY1A L1 L2 RY1B Normally open Common Normally closed External alarm relay contacts set A External alarm relay contac...

Page 10: ...connection NOTES 1 Use of an external filter is required to comply with conducted emissions limits See note 4 below 2 A Line Impedance Stabilization Network LISN was used for conducted emissions measu...

Page 11: ...G All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to properly suppress EMI however...

Page 12: ...n shipment Your P O number Detailed description of the problem Any special instructions Name and phone number of person returning the product 2 Prior approval and an RMA number from the Customer Servi...

Reviews: