Caution
Changing the factory settings may adversely affect the operation
of the boiler.
9.10.3 Control unit settings
Important
All tables show the factory setting for the parameters.
The tables also list parameters that are only applicable if the
boiler is combined with other equipment such as an outdoor
sensor.
All possible options are indicated in the adjustment range. The
display of the boiler only shows the relevant settings for the
appliance.
Tab.30 Navigation for BASIC INSTALLER level
Level
Menu cascade
Basic installer
> Installation Setup > CU-GH08 > Submenu
> Parameters, counters, signals > Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Tab.31 Factory settings at BASIC INSTALLER level
Code
Display text
Description
Range
Gas 120
ACE - 65
Gas 120
ACE - 90
Gas 120
ACE - 115
AP016
CH function on
Enable central heating heat
demand processing
0 = Off
1 = On
1
1
1
AP017
DHW function on Enable domestic hot water
heat demand processing
0 = Off
1 = On
1
1
1
AP073
Summer Winter
Outdoor temperature: upper
limit for heating
10 °C - 30 °C
22
22
22
AP074
Force summer
mode
The heating is stopped. Hot
water is maintained. Force
Summer Mode
0 = Off
1 = On
0
0
0
AP083
Enable master
func
Enable the master functionality
of this device on the S-Bus for
system control
0 = No
1 = Yes
0
0
0
AP089
Installer name
Name of the installer
-
None
None
None
AP090
Installer phone
Telephone number of the
installer
-
0
0
0
CP510
Temporary Room
Setp
Temporary room setpoint per
zone
5 °C - 30 °C
20
20
20
Tab.32 Navigation for INSTALLER level
Level
Menu cascade
Installer
> Installation Setup > CU-GH08 > Submenu
> Parameters, counters, signals > Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
9 Settings
7717201 - v03 - 25062019
MID _HMI T-control - Gas 120 ACE
49