Parameter
Text display
Description
Factory
setting
CP251
CalSondeAmbZone
Calibration of Zone Room Unit
Adjustment range:
from -5 °C to 5 °C
0
CP290
ConfigZonePumpOut
Configuration of Zone Pump Output
Adjustment range:
0 =Zone output
1 =CH mode
2 =DHW mode
3 =Cooling mode
4 =Error report
5 =Burning
6 =Service flag
7 =System error
8 =DHW looping
9 =Primary pump
10 =Buffer pump
0
CP291
ConfigZonePumpOut
Configuration of Zone Pump Output
Adjustment range:
0 =Zone output
1 =CH mode
2 =DHW mode
3 =Cooling mode
4 =Error report
5 =Burning
6 =Service flag
7 =System error
8 =DHW looping
9 =Primary pump
10 =Buffer pump
0
CP320
OperatingZoneMode
Operating mode of the zone
Adjustment range:
0 =Scheduling
1 =Manual
2 =Antifrost
3 =Temporary
1
CP321
OperatingZoneMode
Operating mode of the zone
Adjustment range:
0 =Scheduling
1 =Manual
2 =Antifrost
3 =Temporary
1
CP340
TypeReducedNightMo
de
Type of reduced night mode, stop or maintain heating of circuit
Adjustment range:
0 =Stop heat demand
1 =Continue heat demand
1
CP341
TypeReducedNightMo
de
Type of reduced night mode, stop or maintain heating of circuit
Adjustment range:
0 =Stop heat demand
1 =Continue heat demand
1
CP470
Zone screed drying
Setting of the screed drying program of the zone
Adjustment range:
0 Days =30 Days
0
9 Settings
7717201 - v03 - 25062019
MID _HMI T-control - Gas 120 ACE
55