Tab.33 Factory settings at INSTALLER level
Code
Display text
Description
Range
Gas 120
ACE - 65
Gas 120
ACE - 90
Gas 120
ACE - 115
AP001
BL input setting
Blocking input setting (1: Full
blocking, 2: Partial blocking, 3:
User reset locking)
Blocking input setting (1: Full
blocking, 2: Partial blocking, 3:
User reset locking)
1 = Full blocking
2 = Partial blocking
3 = User reset locking
4 = Backup relieved
5 = Generator relieved
6 = Gen.&Backup
relieved
7 = High, Low Tariff
8 = Photovoltaic HP
Only
9 = PV HP And backup
10 = Smart Grid ready
11 = Heating Cooling
1
1
1
AP008
Time release
signal
The appliance will wait x sec
(0=off) for the release contact
to close in order to start the
burner
0 Sec - 255 Sec
0
0
0
AP009
Service hours
burner
Burning hours before raising a
service notification
0 Hours - 51000 Hours
6000
6000
6000
AP010
Service
notification
The type of service needed
based on burn and powered
hours
0 = None
1 = Custom notification
2 = ABC notification
2
2
2
AP011
Service hours
mains
Hours powered to raise a
service notification
0 Hours - 51000 Hours
35000
35000
35000
AP014
Auto Filling
Setting to enable or disable the
automatic refill device. It can
be set to auto, manual or off
0 = Disabled
1 = Manual
2 = Auto
0
0
0
AP023
Filling Inst
Timeout
Maximum time the automatic
filling procedure may last at
installation
0 Min - 90 Min
10
10
10
AP051
Filling Interval
The minimum time that is
allowed between two top-up
fillings
0 Days - 65535 Days
90
90
90
AP063
CH Set Max
System
Maximum flow temperature
setpoint for burning at central
heating
20 °C - 90 °C
90
90
90
AP069
Top up timeout
Maximum time the automatic
topping up procedure may last
0 Min - 60 Min
2
2
2
AP070
Operational
Pressure
The operational water pressure
the device should be working
on
0 bar - 2.5 bar
1,8
1,8
1,8
AP071
InstallMaxTimeOu
t
Maximum time that is needed
to fill the complete installation
0 Sec - 3600 Sec
0
0
0
AP079
Building Inertia
Inertia of the building used for
heat up speed
0 - 15
3
3
3
AP080
Frost min out
temp
Outside temperature below
which the antifreeze protection
is activated
-60 °C - 25 °C
-10
-10
-10
AP082
Enable daylight
save
Enable daylight saving for the
system to save energy during
winter
0 = Off
1 = On
1
1
1
AP091
Outside Sens.
Source
Type of outside sensor
connection to be used
0 = Auto
1 = Wired sensor
2 = Wireless sensor
3 = Internet measured
4 = None
0
0
0
9 Settings
50
MID _HMI T-control - Gas 120 ACE
7717201 - v03 - 25062019