background image

Tab.33 Factory settings at INSTALLER level

Code

Display text

Description

Range

Gas 120 

ACE - 65

Gas 120 

ACE - 90

Gas 120 

ACE - 115

AP001

BL input setting

Blocking input setting (1: Full 

blocking, 2: Partial blocking, 3: 

User reset locking)

Blocking input setting (1: Full 

blocking, 2: Partial blocking, 3: 

User reset locking)

1 = Full blocking

2 = Partial blocking

3 = User reset locking

4 = Backup relieved

5 = Generator relieved

6 = Gen.&Backup 

relieved

7 = High, Low Tariff

8 = Photovoltaic HP 

Only

9 = PV HP And backup

10 = Smart Grid ready

11 = Heating Cooling

1

1

1

AP008

Time release 

signal

The appliance will wait x sec 

(0=off) for the release contact 

to close in order to start the 

burner

0 Sec - 255 Sec

0

0

0

AP009

Service hours 

burner

Burning hours before raising a 

service notification

0 Hours - 51000 Hours

6000

6000

6000

AP010

Service 

notification

The type of service needed 

based on burn and powered 

hours

0 = None

1 = Custom notification

2 = ABC notification

2

2

2

AP011

Service hours 

mains

Hours powered to raise a 

service notification

0 Hours - 51000 Hours

35000

35000

35000

AP014

Auto Filling

Setting to enable or disable the 

automatic refill device. It can 

be set to auto, manual or off

0 = Disabled

1 = Manual

2 = Auto

0

0

0

AP023

Filling Inst 

Timeout

Maximum time the automatic 

filling procedure may last at 

installation

0 Min - 90 Min

10

10

10

AP051

Filling Interval

The minimum time that is 

allowed between two top-up 

fillings

0 Days - 65535 Days

90

90

90

AP063

CH Set Max 

System

Maximum flow temperature 

setpoint for burning at central 

heating

20 °C - 90 °C

90

90

90

AP069

Top up timeout

Maximum time the automatic 

topping up procedure may last

0 Min - 60 Min

2

2

2

AP070

Operational 

Pressure

The operational water pressure 

the device should be working 

on

0 bar - 2.5 bar

1,8

1,8

1,8

AP071

InstallMaxTimeOu

t

Maximum time that is needed 

to fill the complete installation

0 Sec - 3600 Sec

0

0

0

AP079

Building Inertia

Inertia of the building used for 

heat up speed

0 - 15

3

3

3

AP080

Frost min out 

temp

Outside temperature below 

which the antifreeze protection 

is activated

-60 °C - 25 °C

-10

-10

-10

AP082

Enable daylight 

save

Enable daylight saving for the 

system to save energy during 

winter

0 = Off

1 = On

1

1

1

AP091

Outside Sens. 

Source

Type of outside sensor 

connection to be used

0 = Auto

1 = Wired sensor

2 = Wireless sensor

3 = Internet measured

4 = None

0

0

0

9  Settings

50

MID _HMI T-control - Gas 120 ACE

7717201 - v03 - 25062019

Summary of Contents for Gas 120 ACE - 115

Page 1: ...MW 2000881 02 en MID control box equipped with a HMI T control for Gas 120 ACE boiler...

Page 2: ...sing the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer...

Page 3: ...5 1 Installation regulations 18 5 2 Unpack and fit the control box 18 5 3 Electrical connections 21 5 3 1 Recommendations 21 5 3 2 Electrical power supply 21 5 3 3 Recommended cable cross section 21...

Page 4: ...perature temporarily 42 8 7 4 Timer programming for heating 42 8 8 Domestic hot water temperature 43 8 8 1 Selecting the operating mode 43 8 8 2 Forcing domestic hot water production override 43 8 8 3...

Page 5: ...79 11 Troubleshooting 80 11 1 Displaying and clearing the error memory 80 11 2 Error codes 80 11 2 1 Warning 80 11 2 2 Blockage 81 11 2 3 Lock out codes CU GH 08 83 12 Decommissioning 86 12 1 Decommis...

Page 6: ...r Danger If you smell gas 1 Do not use a naked flame do not smoke do not operate electrical contacts or switches doorbell light motor lift etc 2 Shut off the gas supply 3 Open the windows 4 Locate the...

Page 7: ...ngs the domestic hot water temperature may exceed 65 C 1 1 2 Safety instructions for the user Danger If you smell gas 1 Do not use a naked flame do not smoke do not operate electrical contacts or swit...

Page 8: ...s out to be damaged it must be replaced by the manufacturer its after sales service or persons with similar qualifications in order to obviate any danger Caution A disconnection device must be fitted...

Page 9: ...y of our products we strive constantly to improve them We therefore reserve the right to modify the specifications given in this document Our liability as manufacturer may not be invoked in the follow...

Page 10: ...ioning Get your installer to explain your installation to you Have the required inspections and maintenance carried out by a qualified installer Keep the instruction manuals in good condition close to...

Page 11: ...lt in minor personal injury Caution Risk of material damage Important Please note important information See Reference to other manuals or pages in this manual 2 1 2 Symbols used on the appliance 1 Alt...

Page 12: ...European Directive 2009 125 EC on the ecodesign of energy related products In addition to the legal requirements and guidelines the supplementary guidelines in this manual must also be followed Supple...

Page 13: ...G Y BR BL WH BK RE YE BL GR OR BL YE RE BK OR CB 09 IF 01 8 9 7 2 3 4 6 5 1 1 MID control panel HMI T control 2 Service connector allows the technician to work on the equipment 3 230 V mains power sup...

Page 14: ...F 01 PCB 7 CB 09 PCB 4 3 PCBs 4 3 1 SCB 02 expansion board description Fig 4 SCB 02 expansion board AD 3001313 01 C No Nc Status A C No Nc Status B N L 0 10 Tout N L N 0 10 Tdhw Tflow R Bus The expans...

Page 15: ...ulating pump power connection 4 3 3 Description of the IF 01 PCB The IF 01 PCB is factory fitted and allows additional inputs such as a sensor or switch to be connected to the system This PCB controls...

Page 16: ...exit standby 1 Symbols The selected icon is highlighted 2 Information on the selected icon 3 Navigation level Chimney Sweep level User level Installer level This level is reserved for installers and...

Page 17: ...ting bolts with two serrated washers An outdoor temperature sensor A control box installation user and service manual 4 6 Accessories options A detailed list of accessories and options can be found in...

Page 18: ...d fit the control box Caution Wear gloves when handling the control box 1 Cut and remove the packaging Important The technical documentation is housed in the protective block 2 Remove the two screws f...

Page 19: ...anel 7 Open the control box cover 8 Align the boiler s tapered interlocks with the notches on the control box Fig 11 MW 2000680 03 5 5 Fig 12 MW 6000762 01 6 6 Fig 13 MW 6000763 02 7 90 Fig 14 MW 6000...

Page 20: ...ition by tilting it forwards 14 Lock the control box in position using the two screws and the toothed washers 15 Close the box cover 16 Lock the cover by pressing on the screw head 17 Refit the front...

Page 21: ...he various electrical cables far enough from the heating pipes so that they cannot be damaged by the effect of the heat 5 3 2 Electrical power supply Power supply voltage 230 V AC 50 Hz Caution Please...

Page 22: ...no circumstances be installed in the control panel The sum of the currents from all outlets must not exceed 5 A 5 3 4 Cable routing and access to the connection terminal blocks 1 Unlock the front doo...

Page 23: ...t in a reference room 2 Connect the two wire cable for the thermostat to the R Bus terminals for the connector It does not matter which wire is connected to which terminal block Important If the domes...

Page 24: ...rom the boiler If the outdoor temperature is higher than 10 C no heat demand from the boiler Important The outdoor temperature before the start of frost protection can be changed with the AP080 parame...

Page 25: ...ank sensor NTC 10 k Ohm Tflow Boiler flow temperature sensor NTC 10 k Ohm Tout Outdoor temperature sensor NTC 10 k Ohm The sensor connection contacts are dry contacts 5 3 13 Connecting a tank sensor o...

Page 26: ...cting a standard pump 1 Connect the pump to the X4 terminal on the PCB 5 3 16 Connecting a domestic hot water DHW pump Connecting a domestic hot water DHW pump The maximum power consumption is 300 VA...

Page 27: ...ed contact Contact will close when status occurs Select the desired status notification setting using parameter EP018 and EP019 5 3 20 Connecting 0 10 V output The 0 10 contact can be used to connect...

Page 28: ...l based on temperature or heat output The two controls are described briefly below 1 Connect the input signal to terminals 0 10 of the connector Tab 3 Temperature based control C Jumper 2 Input signal...

Page 29: ...100 Supplied heat output 1 Dependent on the minimum modulation depth set speeds standard 20 5 3 22 Connecting a PC laptop There is a Service connector next to the control panel A Recom interface can b...

Page 30: ...ecifications CIRCA Direct heating circuit Gradient 1 5 Maximum temperature 90 C DHW Domestic hot water circuit Set point temperature 55 C 6 2 Connection example SCB 02 Fig 44 1 boiler 1 mixing zone do...

Page 31: ...Important All the factory settings of the SCB 02 are adequate for this connection 6 Connecting diagrams and configuration 7717201 v03 25062019 MID _HMI T control Gas 120 ACE 31...

Page 32: ...essure in the heating system 6 Check the electricity supply connections to the various boiler components 7 Check the electrical connections on the thermostat and the other external components 8 Check...

Page 33: ...wing the measuring point on the gas valve unit 5 Tighten the pressure socket again when the pipe has been fully vented 6 Check all connections for gas tightness The maximum allowable test pressure is...

Page 34: ...event of an error during start up a message with the corresponding code is displayed The meaning of the error codes can be found in the error table 7 6 2 Shutting down the boiler The boiler must be sh...

Page 35: ...4000 Rpm 1600 1600 1750 GP009 Fan RPM Start Fan speed at appliance start 1000 Rpm 4000 Rpm 2500 2500 2500 Tab 11 Setting for gas type G30 G31 butane propane Code Parameter Description Adjustment range...

Page 36: ...right of the screen 3 Check the load test settings and adjust if necessary Only the parameters shown in bold can be changed Control and setting values for O2 at full load 1 Set the boiler to full loa...

Page 37: ...he load test mode 2 If the full load test was finished select the tile to restart the chimney sweep menu A Change load test mode B MinimumPower 3 Select the MinimumPower test in the menu Change load t...

Page 38: ...the highest and lowest setting limits Allow the pressure to stabilise for approximately 60 seconds between each setting modification Important The boilers are supplied with a variety of gas valve unit...

Page 39: ...g equipment 2 Put the flue gas sampling plug back in place 3 Put the front casing back 4 Bring the heating system temperature up to approximately 50 C 5 Shut down the boiler 6 After about 10 minutes v...

Page 40: ...2 Switching the summer mode on or off You can switch off the central heating function of the boiler to save energy for example during the summer period 1 Select the tile 2 Press the button to confirm...

Page 41: ...ils Set Heating Activity Names Personalise the name of the activities Set Screen Brightness Setting the screen brightness Set click sound Switch the sound of the rotary knob on or off License Informat...

Page 42: ...he temperature settings of activities for the zone selected 1 Select the icon for the zone to be modified for example 2 Select Set Heating Activity Temperatures 3 Select the activity to change its tem...

Page 43: ...programme 8 8 Domestic hot water temperature 8 8 1 Selecting the operating mode For the production of domestic hot water you can choose between five operating modes 1 Select the icon for the DHW zone...

Page 44: ...n activities during the day This can be programmed for each day of the week 1 Select the icon for the DHW zone 2 Select Zone configuration DHW Schedule 3 Select the programme to be modified The progra...

Page 45: ...Heating Curve 3 Set the following parameters Tab 28 Parameter Description Slope Value of the heating curve gradient underfloor heating circuit gradient between 0 4 and 0 7 radiator circuit gradient o...

Page 46: ...n Type of notification Description None No maintenance message Custom notification The maintenance message will be displayed once the burner operating hours defined by the Service Burning hrs paramete...

Page 47: ...detect 9 7 3 Reverting to the commissioning settings If the commissioning settings were saved you can revert to the values specific to your installation To revert to the commissioning settings 1 Press...

Page 48: ...ter Domestic hot water G Gas fired Gas fired heat engine P Producer Central heating Category D codes are appliance controlled only When the domestic hot water is controlled by an SCB it is handled lik...

Page 49: ...ACE 90 Gas 120 ACE 115 AP016 CH function on Enable central heating heat demand processing 0 Off 1 On 1 1 1 AP017 DHW function on Enable domestic hot water heat demand processing 0 Off 1 On 1 1 1 AP073...

Page 50: ...sable the automatic refill device It can be set to auto manual or off 0 Disabled 1 Manual 2 Auto 0 0 0 AP023 Filling Inst Timeout Maximum time the automatic filling procedure may last at installation...

Page 51: ...and Enable manual heat demand function 0 Off 1 With setpoint 2 TOutdoor Control 0 0 0 AP026 Setpoint manual HD Flow temperature setpoint for manual heat demand 10 C 90 C 40 40 40 AP056 Outdoor sensor...

Page 52: ...display Description Factory setting CP000 MaxZoneTFlowSetpoin t Maximum Flow Temperature setpoint zone Adjustment range from 7 C to 90 C 90 CP001 MaxZoneTFlowSetpoin t Maximum Flow Temperature setpoi...

Page 53: ...ed mode that allows switching to comfort mode Adjustment range from 5 C to 30 C 16 CP071 MaxReducedRoomT Li m Max Room Temperature limit of the circuit in reduced mode that allows switching to comfort...

Page 54: ...oint of the zone Adjustment range from 5 C to 30 C 20 CP210 Zone HCZP Comfort Comfort footpoint of the temperature of heat curve of the circuit Adjustment range from 15 C to 90 C 15 CP211 Zone HCZP Co...

Page 55: ...looping 9 Primary pump 10 Buffer pump 0 CP320 OperatingZoneMode Operating mode of the zone Adjustment range 0 Scheduling 1 Manual 2 Antifrost 3 Temporary 1 CP321 OperatingZoneMode Operating mode of th...

Page 56: ...C 20 CP511 Temporary Room Setp Temporary room setpoint per zone Adjustment range from 5 C to 30 C 20 CP520 Zone Power setpoint Power setpoint per zone Adjustment range from 0 to 100 100 CP521 Zone Pow...

Page 57: ...trical Tank 11 DHW Layered Tank 12 Internal Boiler Tank 13 Time Program 0 CP670 ConfPairing RU Zone Configuration of pairing room unit per zone CP671 ConfPairing RU Zone Configuration of pairing room...

Page 58: ...751 MaxZone Preheat time Maximum zone preheat time Adjustment range from 0 Min to 240 Min 60 CP780 Control strategy Selection of the control strategy for the zone Adjustment range 0 Automatic 1 Room T...

Page 59: ...on 11 Locking or Blocking 12 Cooling mode 0 EP028 Function 10V PWM Selects the function of the 0 10 Volt output Adjustment range 0 0 10V 1 Wilo 1 0 10V 2 Gr GENI 2 PWM signal Solar 3 0 10V 1 limited 4...

Page 60: ...ut measured values 9 11 1 Control unit counters Tab 39 Navigation for basic installer level Level Menu path Basic installer Installation Setup CU GH08 Submenu 1 Parameters counters signals Counters 1...

Page 61: ...ve is in DHW position 0 Hours 65534 Hours Tank DHW Gas fired appliance DC004 DHW burner starts Number of burner starts for Domestic Hot Water 0 65534 Internal DHW Tank DHW Gas fired appliance DC005 DH...

Page 62: ...295 CC010 Zone Nbr Pump Starts Numbers of times the pump of the zone has started 0 4294967295 CC011 Zone Nbr Pump Starts Numbers of times the pump of the zone has started 0 4294967295 Tab 47 Mandatory...

Page 63: ...pdate on CAN A Real Time Clock update has been received on the CAN bus 0 No 1 Yes Mandatory bus master Total EnergyConsu Y0 Total energy consumed in the current year 0 kWh 4294967294 kWh Gas fired app...

Page 64: ...detected in the application 0 No 1 Yes Outdoor temperature DM002 DHWFlowSpeed Actual DHW combi flow rate 0 l min 25 l min Internal DHW DM029 DHW setpoint Domestic Hot Water temperature setpoint 0 C 10...

Page 65: ...mp Domestic Hot Water solar tank temperature 25 C 150 C Internal DHW Tank DHW DM008 DHW out temp Temperature sensor for the tap temperature leaving the appliance 25 C 150 C Internal DHW GM025 STB stat...

Page 66: ...functions 40 120 PM P Int Interface Return temp producer Return temperature used for calculations in the power control functions 40 120 PM P Int Interface Wired T Outside Outside temperature measured...

Page 67: ...0 Locking Mode 11 Load test min 12 Load test CH max 13 Load test DHW max 15 Manual Heat Demand 16 Frost Protection 19 Reset In Progress 21 Halted 200 Device Mode 254 Unknown Tab 55 Sub status numbers...

Page 68: ...ure Measure of the room temperature of the zone 0 C 50 C CM050 Status Pump zone Status of the Pump of zone 0 No 1 Yes CM051 Status Pump zone Status of the Pump of zone 0 No 1 Yes CM060 ZonePumpSpeed C...

Page 69: ...etpoint Wished room temperature setpoint of the zone 0 C 50 C CM200 ZoneCurrentHeatMode Displaying current operating mode of the zone 0 Standby 1 Heating 2 Cooling CM201 ZoneCurrentHeatMode Displaying...

Page 70: ...eTRoomUnit setp Room Unit temperature setpoint of zone 0 C 35 C CM111 ZoneTRoomUnit setp Room Unit temperature setpoint of zone 0 C 35 C CM120 ZoneCurrentMode Zone Current Mode 0 Scheduling 1 Manual 2...

Page 71: ...omStp Internal room temperature setpoint calculated by the room temperature controller of the zone 60 C 60 C Tab 58 Zone High Temperatur Zone over heating Active over heating of the zone 0 Off 1 On Zo...

Page 72: ...resent Presense of Room Unit in this zone 0 No 1 Yes CM190 Zone Troom setpoint Wished room temperature setpoint of the zone 0 C 50 C CM191 Zone Troom setpoint Wished room temperature setpoint of the z...

Page 73: ...ctivity Current activity of the zone 0 Anti frost 1 Reduced 2 Comfort 3 Anti legionella CM131 ZoneCurrent activity Current activity of the zone 0 Anti frost 1 Reduced 2 Comfort 3 Anti legionella CM180...

Page 74: ...nction setting 0 Off 1 On AM201 Status contact 1 Status of status contact 1 The meaning is dependant on the current function setting 0 Off 1 On Tab 64 Mandatory for SCB HMI display info Trending strin...

Page 75: ...onal mode active summer winter 0 Winter 1 Frost protection 2 Summer neutral band 3 Summer AP078 Out sensor detected Outside sensor detected in the application 0 No 1 Yes Tab 67 0 10 volt or PWM out Po...

Page 76: ...tem to ensure that there are no leaks Caution Only genuine spare parts may be used 10 2 Maintenance message The boiler display will clearly indicate that a service is required at the appropriate time...

Page 77: ...Set the room thermostat to the highest possible temperature 3 Wait until the radiators are warm 4 Shut down the boiler 5 Wait approximately 10 minutes until the radiators feel cold 6 Bleed the radiat...

Page 78: ...ulic pressure in the installation Caution The hydraulic pressure must reach a minimum of 0 08 MPa 0 8 bar Important If the hydraulic pressure is lower than 0 08 MPa 0 8 bar the bar symbol flashes 2 To...

Page 79: ...o detect after removing or replacing a control PCB Proceed as follows 1 Press the key 2 Select Advanced Service Menu This will send a command to autodetect all devices connected to the Local Bus The s...

Page 80: ...nosis of the type of malfunction and for any technical assistance that may be needed 2 Switch the boiler off and switch it back on 3 The boiler starts up again automatically when the cause of the erro...

Page 81: ...unit makes a number of attempts to restart If the cause of blocking persists the blockage will turn into a fault Press the key to remove the warning from the main display Important If the cause of bl...

Page 82: ...d H02 09 Partial block Partial blocking of the device recognized External cause remove external cause Wrong parameter set check the parameters Bad connection check the connection H02 10 Full Block Ful...

Page 83: ...aulty sensor replace the sensor E00 06 TReturn Missing Return temperature sensor was expected but not detected Bad connection check the wiring and connectors Faulty sensor replace the sensor E00 07 dT...

Page 84: ...ssing E04 01 TFlow Closed Flow temperature sensor is either shorted or measuring a temperature above range Bad connection check the wiring and connectors Incorrectly fitted sensor check that the senso...

Page 85: ...wiring on the ionization ignition electrode E04 11 VPS VPS Gas Valve proving failed E04 12 False flame False flame detected before burner start The burner remains very hot adjust the O2 Ionization cur...

Page 86: ...inside it 6 Remove the pipe connecting the boiler to the chimney and close the nozzle with a plug 12 2 Recommissioning procedure Caution Only qualified professionals are authorised to carry out maint...

Page 87: ...the boiler proceed as follows 1 Switch off the boiler 2 Cut the power supply to the boiler 3 Close the main gas valve 4 Close the water mains 5 Close the gas valve on the boiler 6 Drain the installat...

Page 88: ...lent level of comfort This combination allows you to set the temperature separately for each room However do not install thermostatic radiator valves in the room in which the room thermostat is locate...

Page 89: ...material damage intangible losses or physical injury resulting from an installation that does not comply with Legal or regulatory requirements or provisions laid down by the local authorities National...

Page 90: ...he reference number given in the spare parts list when ordering a spare part Caution Only genuine spare parts may be used 16 2 Spare parts lists 16 2 1 Control panel Fig 65 MW 5000871 1 9 17 22 18 19...

Page 91: ...w x10 13 7685753 24 V control box cable harness 14 7685294 Control panel cable harness RJ11 15 7685149 230 V control box cable harness 16 7704493 SCB 02 PCB 17 7695062 CB 09 PCB 18 7632095 Green 2 pin...

Page 92: ...the products in relation to building size and characteristics Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C Seasonal space heating energy efficiency class of...

Page 93: ...rpolation between the two adjacent values 2 Prated is related to the preferential space heater or combination heater Tab 73 Package efficiency Remeha Gas 120 ACE Gas 120 ACE 65 Gas 120 ACE 90 Gas 120...

Page 94: ...17 Appendix 94 MID _HMI T control Gas 120 ACE 7717201 v03 25062019...

Page 95: ...hnological information contained in these technical instructions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent i...

Page 96: ...o remeha es EST Systems Oy Kujamatintie 16 48720 Kotka FI T 358 50 554 3068 E toimisto estsystems fi Marketbau Remeha Kft Gy r u 2 2040 Budaors HU T 36 23 503 980 F 36 23 503 981 E remeha remeha hu Eu...

Reviews: