Parameter
Description
Adjustment range
Factory setting
CALORA
TOWER GAS
15S EX
CALORA
TOWER GAS
25S EX
CALORA
TOWER GAS
35S EX
p37
Release function (RL)
0 = Hot water on
1 = Release input
1
1
1
p38
Release waiting time
0 to 255 seconds
0
0
0
p39
Gas valve switching time
0 to 255 seconds
0
0
0
p40
Fault relay function
(Optional)
0 = Operation signal
1 = Alarm signal
1
1
1
p41
GpS connected (Optional)
0 = Not connected
1 = Connected
0
0
0
p42
HRU connected (Optional)
0 = Not connected
1 = Connected
0
0
0
p43
Mains detection phase
0 = Stop
1 = Start
0
0
0
p44
Maintenance message
Do not modify
1
1
1
p45
Service operating hours
Do not modify
175
175
175
p46
Service burning hours
Do not modify
30
30
30
p47
(3)
Maximum drop in the DHW
set point when the solar
pump is running at 100%
0 to 30 °C
5
5
5
p48
(4)
Activation of the Titan
Active System® function
0 = No
1 = Yes
1
1
1
p49
Minimum loading time after
burner start-up in DHW
mode
10 to 255 seconds
80
80
80
8Z;5
(5)
Desired domestic hot
water temperature in the
DHW circuit
20 to 80 °C
55
55
55
8Z;M
(5)
Temperature difference
that the solar pump tries to
maintain between the solar
DHW sensor and the panel
100 (x 0.1) to 200 (x 0.1
For example: 215 = 21.5°C
100
100
100
8Z;6
(5)
Temperature of the panel
above which the solar
pump starts up. The pump
does not operate if the
temperature of the solar
tank is higher than 80°C
100 to 125 °C
100
100
100
8Z;7
(5)
Minimum operating
duration of the solar pump
at 100% on start-up
1 to 5 min
1
1
1
8Z;8
(5)
Minimum speed of the
solar pump
50 to 100 %
50
50
50
8Z;G
(5)
Set to 1 if tubular collectors
are used
1 / 0
0
0
0
8Z;H
(5)
Maximum flow rate of the
solar pump
¼
See chapter:
Maximum flow rate of the
solar pump
0 to 20 l/min
6.7
6.7
6.7
(1) Do not modify these factory settings unless absolutely necessary. For example, for modification of the boiler for: G20 (H gas) or G31 (propane),
high pressure systems, WTW coupling or CLV overpressure
(2) Factory setting depends on installation type
(3) The parameter is only displayed if the SCU-S191 and the solar control system are present
(4) The parameter is only displayed if the SCU-S191 is present
(5) The parameter is only displayed if the solar control system is connected
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
6. Commissioning
22/04/2016 - 300026141-001-07
71