9.3.1.
Error readout memorised
1. Press the two keys
f
simultaneously and then key
[+]
until the
symbol
c
flashes on the menu bar.
2. Select the installers menu using the key
S
.
c0de
appears
on the display.
3. Use keys
[-]
or
[+]
to input the installer code
0012
.
4. Press the
S
key.
er[xx
appears on the display.
5. The fault list or shutdown list can be displayed by pressing the
[-]
or
[+]
key.
6. Confirm using key
S
.
er[xx
is displayed with
xx
flashing = Last error which occured, For example
K2
.
7. Use the
[-]
or
[+]
key to scroll through the faults or shutdowns.
8. Press the
S
key to display the details of the faults or shutdowns.
9. Press the
[-]
or
[+]
key to view the following information:
M[1
= Number of times that the error occured.
hr
= The number of operating hours.
5t
= State.
5v
= Sub-status.
t1
= Flow temperature (° F / ° C).
t"
= Return temperature (° F / ° C).
t3
= Calorifier temperature (° F / ° C).
t4
= Outside temperature (° F / ° C) (Only with an outside
temperature sensor).
t5
= Solar boiler temperature (° F / ° C).
5p
= Internal set point (° F / ° C).
fl
= Ionization current (µA).
Mf
= Fan speed in rpm.
pr
= Water pressure (bar (MPa)).
p;
= Supplied relative heat output (%).
10.Press the
>
key to interrupt the display cycle.
er[xx
is
displayed with
xx
flashing = Last error which occured.
11.Use the
[-]
or
[+]
key to scroll through the faults or shutdowns.
12.Press the
>
key to show the fault list or shutdown list.
13.Press 2 times on the key
>
to exit the error memory.
T001530-B
4x
2x
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
9. Troubleshooting
22/04/2016 - 300026141-001-07
91