6.6.2.
Readout from the hour counter and
percentage of successful starts
1. Press the two keys
f
simultaneously and then key
[+]
until the
symbol
\
flashes on the menu bar.
2. Press the
S
key.
hr
and the number of hours of boiler
operation
3600
(for example) are displayed alternately.
3. Press the
[+]
key. The display shows
D
.
hr
is displayed,
alternating with the number of operating hours in central heating
operation
560
(for example).
4. Press the
[+]
key. The display shows
N
.
hr
is displayed,
alternating with the number of operating hours used for heating
tap water
320
(for example).
5. Press the
[+]
key. The display shows
@
.
5Z
is displayed,
alternating with the percentage of successful starts
92
% (for
example).
6. Press the
[+]
key. The display shows
N
.
SOLAR
and the
solar Kwh
45
Kwh (for example) are displayed alternately.
7. Press the
>
key 2 times to return to the current operating
mode.
6.6.3.
Status and sub-status
The information menu
Q
gives the following status and sub-status
numbers:
State
5t
Sub-status
5v
0
Rest
0
Rest (no heat demand)
1
Boiler start (Heat demand)
1
Anti-hunting
2
Control three-way valve (if present)
3
Start pump
4
Wait for the correct temperatures for burner start
2
Burner start up
10
Open flue gas damper/external gas valve
11
Increase fan speed
13
Pre-ventilation
14
Wait for release signal
15
Burner on
17
Pre-ignition
18
Main ignition
19
Flame detection
"0
Intermediate ventilation
L000358-A
5x
2x
Kwh
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
6. Commissioning
22/04/2016 - 300026141-001-07