5.5.6.
Filling the condensate trap
1. Remove the siphon.
2. Fill the siphon with clean water up to the mark.
3. Re-assemble the siphon.
CAUTION
Fill the condensate trap with water before starting the
boiler to avoid combustion products escaping from the
boiler.
5.6
Gas connection
DANGER
Before making the gas connections, ensure that the boiler
is immobilised in accordance with prevailing standards.
1. Connect the gas inlet pipe.
2. Fit a gas stop valve to this pipe in such a way that it is visible and
easily accessible.
3. Connect the gas pipe to the gas shut off valve.
WARNING
4
Close the main gas valve before starting work on the
gas pipes.
4
Before mounting, check that the gas meter has
sufficient capacity. To do this, you should keep in
mind the consumption of all domestic appliances.
4
If the gas meter has a too low capacity, inform the
energy supply company.
1
3
4
5
2
L000181-A
C003098-E
6
6
M002525-A
1
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
5. Installation
22/04/2016 - 300026141-001-07
31