Code
Cause of
the fault
Description
Checking / solution
E
:
07
SU/PCU
The return temperature sensor
is on an open circuit
Bad connection
4
Check the wiring between the PCU PCB and the sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
E
:
08
SU/PCU
Return temperature too low
Bad connection
4
Check the wiring between the PCU PCB and the sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
E
:
09
SU/PCU
Return temperature too high
Bad connection
4
Check the wiring between the PCU PCB and the sensor
4
Check that the SU PCB is correctly in place
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
E
:
10
SU/PCU
Difference between the flow
and return temperatures
insufficient
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
Bad connection
4
Check that the sensor has been correctly fitted
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
4
Check that the heating pump is operating correctly