Parameter
Description
Adjustment range
Factory setting
CALORA
TOWER GAS
15S EX
CALORA
TOWER GAS
25S EX
CALORA
TOWER GAS
35S EX
Zd
Detection of connected
SCUs
0 = No detection
1 = Detection
0
0
0
df
and
dV
Factory setting
To return to the factory settings or
if replacing the PCU PCB, enter
values dF and dU from the
nameplate in parameters
df
and
dV
X
X
X
Y
Y
Y
(1) Do not modify these factory settings unless absolutely necessary. For example, for modification of the boiler for: G20 (H gas) or G31 (propane),
high pressure systems, WTW coupling or CLV overpressure
(2) Factory setting depends on installation type
(3) The parameter is only displayed if the SCU-S191 and the solar control system are present
(4) The parameter is only displayed if the SCU-S191 is present
(5) The parameter is only displayed if the solar control system is connected
n
Maximum flow rate of the solar pump (if connected)
In order for the regulator to calculate the quantity of heat produced by
the installation (parameter kWh), input parameter
SO07
. The
parameter
SO07
is equal to the flow in litres per minute in the
solar circuit.
Establish the
SO07
value with the help of the table below,
according to the configuration of the installation and the number or
surface area of collectors.
When the flow is input incorrectly, the display kWh will also be
incorrect.
The quantity of heat (kWh value) can only be used for
checks carried out for personal reasons.
Flat solar collectors
Solar panel
installation
Area (m
2
) Number of
panels
Flow rate
(l/h)
Flow rate
(l/min)
3...5
1 or 2
400
6,7
6...8
3 or 4
300
5,0
8...10
4 or 5
250
4,1
8...10
2x2
750
12,5
12...15
2x3
670
11,2
16...20
2x4
450
7,5
12...15
3x2
850
14,2
18...23
3x3
800
13,4
24...30
3x4
650
10,9
16...20
4x2
1200
20,0
24...30
4x3
850
14,2
6. Commissioning
CALORA TOWER GAS 15S EX CALORA TOWER GAS 25S EX
CALORA TOWER GAS 35S EX
72
22/04/2016 - 300026141-001-07