Fault Finding Chart 1.5
1.5
Is an external time clock
or switch fitted?
NO
1.6
Is external switch or time
clock on?
YES
NO
YES
YES
External switch or time clock
must be on for burner to
operate.
Is 24 volts present at
relay 2 coil?
YES
Repair O/C wiring.
NO
Are relay 2 contacts 6 & 4
closed?
YES
Replace relay 2.
NO
Are relay 1 contacts 6 & 4
closed?
YES
Replace relay 1.
NO
4
NO
Is there 24 volts at relay 1
coil?
Repair O/C wiring.
NO
Are 55ºC outlet high limit
contacts closed?
YES
4
Is 24 volts present at the
ignition module?
NO
YES
Repair O/C wiring.
NO
Test 12
Test 13
Test 14
Test 15
Test 16
Test 17
Test 18
55ºC outlet high limit has tripped
Is the ignition module
giving 4 flash indication?
45ºC inlet high limit has tripped
NO
Replace ignition module.
YES
Refer to section on ignition
module
Are 45ºC inlet high limit
contacts closed?
YES
A
Does the heater have an
auto reset PCB?
NO
Is 24 volts present at auto
reset safety PCB inputs?
YES
Is 24 volts present at auto
reset safety PCB output?
YES
Replace auto reset safety
PCB.
NO
A
YES
Test 22
Test 23
Repair O/C wiring.
NO