TM018 Raypak 131 Type A Pool & Spa Heaters REV: A
D.O.I: 8/04/2009
This document is stored and maintained electronically by
Service. All printed copies not bearing this statement in RED are deemed “uncontrolled”
15
Operational Flow Chart 2
Flame signal
lost? (< 0.2µA)
YES
Water temp = Set
temp + 0.5ºC?
NO
Ignition
& flame
proving
(15 sec
max)
Burner
operation
45º high limit
contacts open?
NO
External switch or
time switch
contacts open?
NO
Water pressure
switch contacts
open?
55º high limit
contacts
open?
2
NO
NO
3
YES
4
YES
5
YES
YES
NO
YES
YES
Flame signal >
0.2µA detected?
Internal check
ok?
NO
NO
NO
YES
System
check
(3 sec)
Approx
5 sec
Flame signal >
0.2µA detected?
NO
Flame signal >
0.2µA detected?
YES
D
D
Ignitor current
draw > 1.4A?
YES
YES
Has 15 sec
‟s
expired since
igniter on?
NO
YES
E
E
NO
Igniter on
Gas valve energised
Gas valve opens
Igniter off
Igniter off
Relay 1 de-energised
Gas valve
de-energised
Gas valve
de-energised
Gas valve closes
Gas valve closes
Ignition module
de-energised
Ignition module
de-energised
Gas valve
de-energised
Ignition module
de-energised
Control board ends
call for heat
Ignition module 3
flash indication
Ignition module
3 flash indication
Ignition module
4 flash indication
Ignition module
energised
LOCKOUT
Gas valve closes
Gas valve de-
energised
Turn controller on
Turn controller off
Igniter off
False Flame
Flame Failure
Relay 2
de-energised
Gas valve closes
5 sec
delay