63
i4000 Lattice Crane
Instruction Manual
55M4000EBE00 Rev C
5.5.2 External peripherals
The i4000 system can communicate with 1 angle/length interface. Each sensor is activated
through the calibration menu in the ‘‘Enable/Disable sensors’’section.
A) Angle / Length interface and A2B errors
Error message
Runtime process
Error cause
Angle 1: Sensor fail
The value of the sensor’s
signal in volts is not valid (1
to 4 volts).
1) The 12 bit converter or
accelerometer is faulty.
Angle 1: In prod. Cal
Indicates that the angle interface is
in pre calibration mode.
Angle 1: Lost
communication
The system has not received
a valid message from the
Angle interface within the
required time frame.
1) The Angle interface is faulty.
2) The cable linking the interface to
the bus CAN network is broken.
Angle 1: Is not calib.
The Angle sensor is not calibrated.
Angle 1: DR+ fail
The 5 Volts reference
tension is not valid (If < 4.5
volts or > 5.5 volts).
The Angle interface circuit is faulty.