Raisecom
iTN8600-I (A) Product Description
4 Technical specifications
Raisecom Proprietary and Confidential
Copyright © Raisecom Technology Co., Ltd.
30
Parameter
Description
Relative humidity
10%–90% RH (non-condensing)
Temperature change rate (°C/min)
≤ 0.5
)
≤ 700
)
≤ 600
Wind speed (m/s)
≤ 5
Biotic environment
Keep the iTN8600-I away from:
Microorganism, such as fungus and mould
Rodent animals, such as rats
Air cleanliness
There should not be any explosive, electro-conductive, magneto-conductive, or corrosive
substance.
Table 4-10 lists concentration requirements for the mechanical active substance in operation.
Table 4-10
Concentration requirements for the mechanical active substance in operation
Mechanical active substance
Concentration
Dust grain (grain/m³
)
≤ 3 × 10
5
Suspending dust (mg/m³
)
≤ 0.2
Droppable dust (mg/m³
h)
≤ 15
Grit (mg/m³
)
≤ 100
Table 4-11 lists concentration requirements for the chemical active substance in operation.
Table 4-11
Concentration requirements for the chemical active substance in operation
Chemical active substance
Concentration
SO
2
(mg/m³
)
≤ 0.30
H
2
S (mg/m³
)
≤ 0.10
NH
3
(mg/m³
)
≤ 3.00
Cl
2
(mg/m³
)
≤ 0.10
HCl (mg/m³
)
≤ 0.10
HF (mg/m³
)
≤ 0.01