RME EAGLE User Manual
Rain Master Irrigation Systems
Page 80
Chapter 6 Setup Key Operations
Then:
•
Set the flow percentage to 15 percent.
•
Run Automatic LIMITS (see next section) for all stations.
•
The new limits will be automatically saved (nominal measured flow + 15 percent)
for each station.
2.
Your system has been operational for some time. Occasionally, one or more stations
seemingly at random fail the flow upper limit. Upon physical inspection of the stations
everything appears fine. Upon further investigation it is determined that there are large
fluctuations in the static water pressure. It is desired to bump all stations from their existing
15 percent (above nominal) to 25 percent (above nominal).
Then:
•
Set the flow percentage to 25 percent.
•
All station limits will now be recalculated to provide another 25 percent over the
initial nominal readings.
NOTE:
This SETUP function will be skipped if you have not enabled the flow
features.
EXAMPLE:
Assume the initial measured flow (nominal value) was 40 GPM for a station.
Because the flow percentage was originally 15% then the station upper limit as
retained in the controller is 46 GPM (1.15 x 40). Now, setting the new flow
percentage of 25% yields a new station limit of 50 GPM (1.25 x 40).
Continue
to
Press:
Until display indicates:
Press:
Display will indicate:
Press:
The controller will return to the Automatic Mode.
PERCNT25
PROGRAM
SETUP
P E R C N T 1 5
PROGRAM
ENTER
QUIT
2
MON
5
THU