RME EAGLE User Manual
Rain Master Irrigation Systems
Page 108
Chapter 9 Troubleshooting
•
FAULT…PRESS…REVIEW…will appear in the display.
•
The controller will continue to execute programs; however, any faulted station(s) will not be
turned on again.
NOTE:
If multiple stations are on simultaneously, and the controller detects an
No Flow Station fault, all running stations will be diagnosed as faulty.
User Action:
1.
Check for:
a. An improperly adjusted valve (valve does not come on even if 24 VAC is applied).
b. Check the field wiring from the controller to the valve. This can be accomplished by
turning the valve on using the controller’s front panel (see 5.7.2 MANUAL Station)
and measuring 24 VAC directly at the valve.
c. If all stations indicate “NO FLOW” check the following:
•
Flow Sensor wiring and setup.
•
Proper operation of Master Valve and/or the Pump.
•
Main water supply to the system.
When corrective action has been completed, the fault must be cleared by you.