Instruction Book
9828 0934 73
129
Unit
•
Ambient air temperature 77 °F
Compressed air inlet temperature 95 °F
Cooling water inlet temperature 77 °F
hp
1.98
2.95
3.73
•
Ambient air temperature 38 °C
Compressed air inlet temperature 38 °C
Cooling water inlet temperature 29 °C
kW
2.3
2.6
3.0
•
Ambient air temperature 100 °F
Compressed air inlet temperature 100 °F
Cooling water inlet temperature 84 °F
hp
3.08
3.49
4.02
•
Ambient air temperature 40 °C
Compressed air inlet temperature 50 °C
Cooling water inlet temperature 40 °C
kW
3.14
3.72
4.6
•
Ambient air temperature 104 °F
Compressed air inlet temperature 122 °F
Cooling water inlet temperature 104 °F
hp
4.21
4.99
6.17
Cooling medium flow
Economy mode
•
Ambient air temperature 25 °C
Compressed air inlet temperature 35 °C
Cooling water inlet temperature 25 °C
l/s
0.2
0.3
0.4
•
Ambient air temperature 77 °F
Compressed air inlet temperature 95 °F
Cooling water inlet temperature 77 °F
cfm
0.42
0.64
0.85
•
Ambient air temperature 40 °C
Compressed air inlet temperature 50 °C
Cooling water inlet temperature 40 °C
l/s
1.5
1.3
1.5
•
Ambient air temperature 104 °F
Compressed air inlet temperature 122 °F
Cooling water inlet temperature 104 °F
cfm
3.18
2.75
3.18
Maximum saving mode
•
Ambient air temperature 25 °C
Compressed air inlet temperature 35 °C
Cooling water inlet temperature 25 °C
l/s
0.2
0.3
0.4
•
Ambient air temperature 77 °F
Compressed air inlet temperature 95 °F
Cooling water inlet temperature 77 °F
cfm
0.42
0.64
0.85
•
Ambient air temperature 40 °C
Compressed air inlet temperature 50 °C
Cooling water inlet temperature 40 °C
l/s
1.5
1.3
1.5
•
Ambient air temperature 104 °F
Compressed air inlet temperature 122 °F
Cooling water inlet temperature 104 °F
cfm
3.18
2.75
3.18
Lowest dewpoint mode
•
Ambient air temperature 25 °C
Compressed air inlet temperature 35 °C
l/s
0.2
0.3
0.4
QPVS650
QPVS850
QPVS1050